Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100016 © Pfannenberg GmbH
Page 33 / 43
GB
Error messages
Error
no.
Fault
Unit activity
Possible causes
Corrective measures
Er15
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Blinking
OFF
OFF
OFF
OFF
Open
Anti-freeze (optional):
Anti-
freeze sensor ≤ 1°C.
Safety shut-off, because
there is a risk of icing of
the compressor.
Restart after
accumulating
condensate water has
evaporated.
A restart is only possible
with disconnection and
re-connection of the
mains voltage.
For safety reasons, there
is no other means of
resetting.
Clean the heat
exchanger fins
(internal/external).
Inspect the switch
cabinet for leaks.
Select higher switch
cabinet temperature
setpoint.
Check function of the
evaporator fan
(internal).
Er19
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Blinking
OFF
OFF
OFF
OFF
Open
Sensor 5 (TS5) defective
Replace Sensor 5 or the
controller circuit board
according to the unit
type.