Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100016 © Pfannenberg GmbH
Page 23 / 43
GB
3.5.4
Mains supply connection
WARNING
Potential danger due to incorrect cables
An incorrect cable cross-section will cause the cable to overheat. Scorched insulation can cause fires.
The cable cross-section (4) matches the output required for the power consumption and is
0.5
– 2.5mm² or AWG 20 to AWG 14.
The following general requirements must be ensured for safe and reliable operation of the cooling units:
• Upstream installation of a supply-side temperature regulator is prohibited.
• Connect the upstream fuse specified on the type plate as wiring protection; see
Type plate
and Adapting the
upstream fuse
.
• Ensure that the type plate specifications for rated values match the present values for mains voltage and mains
frequency; see
Type plate.
• Always connect the cooling unit to the mains by means of a separating device (switch/contactor).
The separating device must have a contact opening of 3 mm. The separating device is installed by the
customer.