Pfannenberg DTI 4x01 Series Скачать руководство пользователя страница 12

GB

985408004 

12/20 

8.4  Power connection 

CAUTION!   

• The cooling unit must be connected to the mains by means of a

disconnecting  device  with  a  contact  gap  of  at  least  3  mm  when
switched off.

• No temperature control must be series-connected to the cooling

unit feed.

The fuse as indicated on the ID plate must be series-connected as 
line protection. 
•Power  connection  and  repairs,  if  applicable,  may  only  be  carried
out by authorized trained electricians.

Power supply connection (mains):

Both mains voltage and frequency must correspond to the nominal 
values indicated on the ID plate of the cooling unit.  
• The  installation of  the  power  cable  is  not  subject  to  any  special

requirements

Attention: The cooling unit may be damaged if the 
voltage is too high. 

Refers to cooling units for nominal voltages 400 V/460V. 
As  an  option,  some  units,  different  to  the  standard  (400 
V/460  V),  may  be  connected  to  a  different  mains  voltage 
(For voltage range see enclosed sheet).The feed cables on 
the transformer primary must be unclamped for this. 

8.5  Service interface 

The service interface is only intended for temporary data exchange 
and not for continuous operation. 

Operating Conditions 

• Voltage  must  be  within  ±  10  %  of  the  value  indicated.

Frequency must be within ± 3 Hz of the value indicated.

• Ambient  temperature  must  be  below  55  °C  (for  options  see

supplement).

• Use  the  unit  such  that  the  cooling  capacity  suits  the  actual  de-

mand.

• Use refrigerant as indicated only.
• Use genuine spare parts only.

10  Putting into operation and function 

10.1   General remarks 

The  cooling  unit  is  provided  with  an  electronic  control  system.  The 
drawn-in  switch  cabinet  internal  air  temperature  is  measured  by  a 
temperature  sensor.  By  means  of  a  DIP  switch  on  the  standard 
control board, different switch cabinet temperatures as well as upper 
limit temperatures can be selected (see accompanying supplement 
sheet). 
Exceeding the limit temperature generates an alarm. For units with 
Multi-Controller, the lower temperature limit can also be monitored. 

Warning! 

Ambient  conditions  and  temperature  in  the  switch  cabinet 
must be in accordance with the values indicated in the sup-
plement.

Содержание DTI 4x01 Series

Страница 1: ...embutidas DTS e DTI 4x01 de climatiza o Operating and assembly instructions for side mounted and built in cooling units DTS and DTI 4x01 Instrucciones de la instalaci n y del uso de acondicionadores...

Страница 2: ...s embutidas DTS e DTI 4x01 de climatiza o 3 Operating and assembly instructions for side mounted and built in cooling units DTS and DTI 4x01 9 Instrucciones de la instalaci n y del uso de acondicionad...

Страница 3: ...enda es de seguran a e outras informa es est o estruturadas da seguinte forma PERIGO Se as medidas descritas a seguir n o forem rigorosamente observadas h perigo para a vida e a sa de PERIGO Se as med...

Страница 4: ...trico deve ser verificado regularmente Qualquer falha como liga es soltas ou cabos queimados deve ser removida imediatamente Os trabalhos no equipamento de refrigera o e nos componentes el ctricos s...

Страница 5: ...ixo 3 Aperte os dois parafusos que s o enviados na embalagem no ponto superior de fixa o da unidade de refrigera o Posicione a unidade no painel el trico com o auxilio dos parafusos de i amento 4 Util...

Страница 6: ...valor indicado A temperatura ambiente deve estar abaixo de 55 C para outras op es verificar ficha complementar Use a unidade de modo que a capacidade de resfriamento seja adequada demanda real Use so...

Страница 7: ...regularmente Os intervalos de limpeza ou os intervalos de substitui o da manta dependem principalmente das condi es ambientais polui o do ar Voc pode lavar a manta utilizando gua aquecida a 40 C e de...

Страница 8: ...a porta e eliminar pontos de fuga no painel el trico O condensado n o drenado O dreno de condensado est obstru do Limpar o dreno de condensado A mangueira de sa da de condensado precisa ser colocada...

Страница 9: ...ved there is danger to life and health due to electrical shock CAUTION If the measures described in the following are not strictly observed material damage may be caused Hint A hint contains additiona...

Страница 10: ...faults such as loose connections or scorched cables must be removed immedi ately Work on the cooling system and on electrical components may only be carried out by authorized specialist personnel Com...

Страница 11: ...the screws nuts and washers included in the component pack to secure the cooling unit on the inner side of the switch cabinet Tighten up fixings so that the seal is compressed to a thickness of 2 mm 5...

Страница 12: ...on the transformer primary must be unclamped for this 8 5 Service interface The service interface is only intended for temporary data exchange and not for continuous operation 9 Operating Conditions V...

Страница 13: ...be compressed or damaged during the cleaning process CAUTION Damage to electric connections on the covering hood If the covering hood is removed the electric plug in connec tions on the inside must be...

Страница 14: ...ondensate fails to drain Condensate drainage clogged Clean condensate drainage Condensate drainage hose must be inclined downward without showing a bend Condensate runs out of the unit The condensate...

Страница 15: ...debido a descargas el ctricas si no se observan estrictamente las medidas descritas a continuaci n PRECAUCION Significado si no se observan estrictamente las medidas descritas a continuaci n se puede...

Страница 16: ...ejando sin efecto cualquier tipo de garant a El equipo el ctrico debe comprobarse peri dicamente Cualquier anomal a tal como conexiones flojas o cables chamuscados debe corregirse inmediatamente Los t...

Страница 17: ...rnos roscados que est n adjuntos en el paquete de piezas suministrado en los puntos de fijaci n supe riores del acondicionador Colgar el equipo por medio de los pernos roscados desde afuera en el arma...

Страница 18: ...iginales 10 Puesta en marcha y funcionamiento 10 1 Generalidades El acondicionador est equipado con un control electr nico A trav s del sensor de temperatura se registra la temperatura del aire aspira...

Страница 19: ...la alfombrilla del filtro Evite usar un chorro de agua demasiado fuerte Si la alfombrilla del filtro tiene aceite o grasa sustit yala 11 2 Mantenimiento El circuito de refrigeraci n como sistema herm...

Страница 20: ...erta del armario el ctrico Corrija la fuga en el armario el ctrico La condensaci n no se drena Drenaje de condensaci n obturado Limpie el drenaje de los condensados La manguera de drenaje de condensac...

Отзывы: