VersiSafe
11
Contacts 11/12, 23/24,
33/34, 43/44 against each others:
4 kV / 2
Indicator contact 53/54
against all others:
4 kV / 2
Semiconductor outputs A3+/
ON / ERR / A4 against all others:
6 kV / 2
Auxiliary voltage A1 / A2
against all others
at auxiliary voltage AC:
6 kV / 2
at auxiliary voltage DC:
4 kV / 2
Control terminal X1 / X2 / X3:
no galvanic separation to L1 / L2 / L3
EMC
IEC/EN 62 061
Interference suppression
Auxiliary voltage AC:
limit value class B
EN 55 011
Auxiliary voltage DC:
limit value class A*)
EN 55 011
*) The device is designed for the usage under industrial conditions (Class A, EN 55011). When
connected to a low voltage public system (Class B, EN 55011) radio interference can be
generated. To avoid this, appropriate measures have to be taken.
Degree of protection
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Enclosure:
thermoplastic with VO behaviour
according to UL subject 94
Vibration resistance:
amplitude 0,35 mm
frequency 10 ... 55 Hz
IEC/EN 60 068-2-6
Climate resistance:
25 / 060 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire connection:
DIN 46 228-1/-2/-3/-4
Screw terminals (integrated):
1 x 4 mm
2
solid or
1 x 2,5 mm
2
stranded ferruled or
2 x 1,5 mm
2
stranded ferruled or
2 x 2,5 mm
2
solid
Insulation of wires
or sleeve length:
8 mm
Wire fixing:
Plus-minus terminal screws M 3,5
box terminal with wire protection or
cage clamp terminals
Mounting
DIN rail
IEC/EN 60 715
Weight:
approx. 400 g