As opposed
to the thermal differential, the temperature can be adjusted
MODULATING PROPORTIONALLY (P OP)
r
setting cycles from 7 to 20
minutes (default 10 minutes).
This system maintains the desired temperature more stable, whilst
increasing the user's comfort sensation and saving on energy
consumption.
A long cycle is recommended for systems with high thermal inertia (cast
iron radiators, floor systems) and a short cycle for systems with low
thermal inertia (fan coils).
ON
OFF
ON
OFF
ON
T SET
thermal inertia over temperature
of the heating element
time
°C/°F
example of modulating proportional adjustment
OFF
With the keys
select la item
Set REG
.
Press
to confirm.
OK
It will be possible to select temperature adjustment mode between
Thermal differential (On:OFF)
Modulating
factory setting or
proportional (PrOP)
operation.
Use the
keys to select the desired temperature adjustment mode.
After making your choice press
to confirm and display the screen to set
OK
HYSTERESIS
On:OFF,
PERIOD
if you have opted for
or to set the
if you have
opted for
(see next paragraphs:
PrOP
11.2.2 e 11.2.3).
From normal thermostat operation, access the menus by pressing
the «
» key, select
press
to confirm.
for 5 secs.
M
OK
ode
Set Prog,
/OK
11 - CONFIGURATION MENU (installer)
EN
38
11.2.1 - Selection of the temperature adjustment mode ( ifferential ON/OFF or
roportional)
D
P