INSTALLATION INSTRUCTIONS
OVERALL DIMENSIONS
surface mounted
120
82
40
27,5
CURRENTLY NATIONAL STANDARDS ENFORCEABLE IN THE INSTALLATION
COUNTRY COVERING THE INSTALLATION AND USE OF GAS POWERED
EQUIPMENT ARE TO BE RESPECTED, AS ARE STANDARDS COVERING SMOKE
DISPERSION AND VENTILATION OF ENCLOSED AREAS, EVEN THOUGH GAS
DETECTION EQUIPMENT IS INSTALLED.
min. 1 m
max. 4 m
Natural gas detector
min. 1 m
max. 4 m
LPG detector
Fig. 7
•
Install Natural Gas detector
max. 30 cm from ceiling
.
•
Install LPG detector
.
max. 30 cm from floor
•
Install detectors from 1 to 4 m from gas appliances.
•
Do not install the detectors outdoors or in places exposed to atmospheric agents.
•
Do not install the detectors near: sink, air vents, HVAC appliances or windows;
furthermore, the detectors must not be installed in enclosed spaces, such as
behind a curtain or inside a closet.
Fig. 8
Example of installation
1.i - INSTALLATION OPERATIONS
Solenoid valve
13
4.u - ADVICES FOR CORRECT USE
•DO NOT bring cloths soaked with Alcohol, Acetone, Ammonia,
Bleach or Solvents into the proximity of the appliance.
•DO NOT use any kind of SPRAY near the gas detector.
• DO NOT carry out an operational test on the gas detector by
releasing gas directly from the gas pipe, lighters or lighter refill
cans.
•Cooking vapours and pollutant dusts can affect the
performance of the sensor over time.
•DO NOT ATTEMP TO OPEN THE CABINET: danger of electric
shock and malfunctions.
• On a periodic basis, check that the vents on the front panel of
the detector, which channel air to the sensor, are not
obstructed by dust or grease, etc.
•To clean this device make use of a lightly wet tissue.
semi flush mounted
(with optional support may
be purchased separately)
EN
max 30 cm
max 30 cm
Note
: in residential units with
several floors, communicating with
each other, additional gas
detectors must be installed.