Perlight Solar PLM-OM Series Installation Manual

7

www.perlight.com

V.01.2022 A1.0

Installation Safety

Abide by the safety regulations for all other modules used in the PV system, including 

wiring and cables, connectors, controllers, inverters, storage batteries, etc., and use suitable 

equipment, connectors, wiring and mounting system for a PV system. If the PV system is 

used in storage batteries, the configuration with the modules should follow the advice of the 

storage batteries manufacturer. The same size, the same specifications of the model can be 

connected in series.

Do not install or handle the modules when they are wet or during strong wind. Keep the 

junction box’s cover closed.

Damaged modules have the risk of electric shock and fire, such modules cannot be repaired 

and should be replaced immediately.

When exposed to direct sunlight, one individual solar module may generate DC voltages 

greater than 30 volts.

To reduce the risk of electric shock or burning, you can install modules with opaque material 

on the surface of the module. The mounting of the array of modules must be carried out with 

an isolating solar installation. Do not wear metal rings, watches, earrings and other metal 

accessories when installing or servicing PV systems. Do not touch the electrical parts of the 

module directly by hand. Use an insulated tool to make electrical connections and keep the 

tool dry.

The triangular holes on the backside frame of the module are drainage holes which cannot be 

blocked.

The maximum system voltage indicated in the rating label is 1500 V. During the system 

Installation, the maximum open circuit voltage in series cannot exceed the maximum system 

voltage.

During module interconnection, ensure to fix the connecting cables to supporting mounting 

frame, so as to restrict cable movement.

Abide by the allowable minimum bending radius of the cables (suggest no less than 43mm).

Always protect the cable with conduit where there is a risk of animals or children coming into 

contact with it. 

Use connectors which are specially designed for photovoltaic systems, and assemble with the 

tools recommended or specified by the manufacturer. In case that the connector applicable to 

the solar system is required, please contact your local supplier. Only connectors of the same 

type must be used.

Make sure that the polarity is correct when connecting the module with inverter, storage 

battery or combiner box to avoid damage to bypass diodes in the modules due to incorrect 

polarity.

Do not drill holes in the frame, this may reduce the mechanical load ability and cause 

corrosion of the frame.

Do not scratch the anodized coating of the frame (except for grounding connection), this may 

cause corrosion of the frame or reduce the mechanical load ability.

Modules can’t be used to replace the roof and wall materials, partial replacement is not 

allowed.

Any part (including nameplate) of modules supplied by Perlight Solar Co., Ltd can’t be 

dismantled without permission.

Содержание PLM-OM Series

Страница 1: ...Perlight Solar PLM OM Series Installation Manual ...

Страница 2: ...www perlight com V 01 2022 A1 0 Table of Contents 1 Introduction 3 2 Applicable Modules 4 4 Warning and Notes 5 9 5 Identification 9 6 Module Structure 10 7 Mounting and Notes 11 13 8 Grounding 14 9 Module Wiring 15 10 Maintenance 16 17 11 Recycling 18 ...

Страница 3: ...nce and in case of sale or disposal of the solar modules This manual does not constitute a warranty expressed or implied Perlight does not assume responsibility and expressly disclaims liability for loss damage or expense arising out of or in any way connected with installation operation use or maintenance of the solar modules The mechanical and electrical installation of the solar modules shall b...

Страница 4: ...xxxOM2B 66 PLM xxxOM2A 66 PLM xxxOM 66B PLM xxxOM2 66B PLM xxxOM2B 66B PLM xxxOM2A 66B PLM xxxOM6 60 PLM xxxOM6B 60 PLM xxxOM6A 60 PLM xxxOM6 60B PLM xxxOM6B 60B PLM xxxOM6A 60B PLM xxxOM10 68 PLM xxxOM10 68B PLM xxxOM10 57 PLM xxxOM10 57B Module dimensions and electrical performance data are detailed in the corresponding technical specification datasheets Module electrical performance parameters ...

Страница 5: ...ght Solar PV module output Refer to local and national Electrical Code for any additional multiplying factors which may also be applicable General Safety Perlight Solar s modules have been evaluated by according to IEC61215 and IEC61730 application class A modules rated for use in this application class may be used in system operating at greater than 50V DC or 240W The safety class of the module i...

Страница 6: ...d in this manual when cleaning Handling Safety Do not open the box until it reaches the installation location Keep the package dry and in a dry place Please refer to the Unpacking manual of standard packaging of Perlight Solar photovoltaic modules During all handling procedures make sure that the modules are not subject to large vibrations that the modules fall to the floor or that objects fall on...

Страница 7: ...ool dry The triangular holes on the backside frame of the module are drainage holes which cannot be blocked The maximum system voltage indicated in the rating label is 1500 V During the system Installation the maximum open circuit voltage in series cannot exceed the maximum system voltage During module interconnection ensure to fix the connecting cables to supporting mounting frame so as to restri...

Страница 8: ...urface shall not be partly shaded by trees building clothes tools packaging materials etc because these objects will form shadow in the module surface leading to loss of system output power The module shall be installed in a well ventilated place meanwhile enough space for airflow shall be allowed at the back and sides of the module so that the heat generated during operation can be radiated Modul...

Страница 9: ... during the winter External or otherwise artificially concentrated sunlight shall not be directed onto the front or back face of the PV module 5 Identification Each PV module is affixed with two kinds of labels providing the following information 1 Label Describes the product name PV module model nominal power rated voltage rated current open circuit voltage short circuit current maximum system vo...

Страница 10: ...Perlight Solar PLM OM Series Installation Manual 10 www perlight com V 01 2022 A1 0 6 Module Structure Module Rear mm Module Front Side mm Mounting hole mm Frame size mm ...

Страница 11: ...he appropriate local and civil codes prior to installation Perlight Solar modules can be mounted using the following methods Direct fixing to mounting structure Suitable module clamps as part of solar mounting system Insertion systems Roof integrated systems Direct Fixing to Mounting Structure 2400Pa Wind Load 2400Pa Snow Load 5400Pa Wind Load 3800Pa Snow Load Use Four Mounting Holes Use Eight Mou...

Страница 12: ...ule mounting clamps must not come into contact with the front glass and must not deform the frame Module clamps should not cause shadowing effects It is not permitted to modify the module frame under any circumstances Recommended distance between two modules is 5mm considering linear thermal expansion of the module frames Clearance between the module frame and mounting surface may be required to p...

Страница 13: ...ign may have an impact on fire resistance If the modules are to be installed on the roof or wall of a building using an integrated mounting system the fire resistance of roof covering or wall should be rated for the application and certified for use to local and national standards Here the stand off method or the rack method is recommended The modules are supported parallel to the surface of the b...

Страница 14: ...delines The grounding conductor must then make a connection to earth using a suitable earth ground electrode Attach a separate conductor to one of the marked 4mm diameter grounding holes on the module frame with a bolt and nut that incorporates an external tooth washer This is to ensure positive electrical contact with the frame The rack must also be grounded unless they are mechanically connected...

Страница 15: ...ns where wiring is exposed to the direct rays of the Sun Field connections Connecting cables should be a minimum of 12 AWG copper cables which are UV resistant and insulated for a minimum of 90 C All wiring and electrical connections must comply with local and national Electrical Code Blocking Diodes In a system utilizing a battery blocking diodes are typically placed between the battery and the s...

Страница 16: ...ency of cleaning depends on the rate of dirt build up Under normal conditions the rain will clean the surface of the module but it is still required to regularly clean the module surface using a soft sponge or cloth dry or wet Never use a rough surfaced material to clean modules do not use acid and alkali cleaner to remove dirt Avoid pressing hard during cleaning which may cause glass deformation ...

Страница 17: ...s c Check the module backsheet whether there is hot negative film raised signs of burns or scorching and so on d Check whether the encapsulation materials of the module have delamination bubbles etc e Check the tightness of the bolts and the electrical connections at the connection points between the modules and the supporting rail Inspection of connectors and cables It is advisable to carry out a...

Страница 18: ... to produce electricity for a minimum of 25 years however the panels may continue to offer useful energy for years to come after this point Once the panels reach the end of their useful life they should be recycled in accordance with local guidelines and regulations Within the European Union solar modules are subject to Waste Electrical and Electronic Equipment WEEE regulations The WEEE symbol is ...

Страница 19: ...Perlight Solar Co Ltd Address Oufeng Road Muyu Zeguo Town Wenling City Zhejiang Province 317521 China Tel 0086 576 86477920 www perlight com enquiry perlight com ...

Отзывы: