9. Module Wiring
Each solar module is wired with two separate series cell strings.
Bypass Diodes
Bypass diodes are wired in parallel with the series cell strings to prevent hot spot heating
caused by individual cell reverse bias that occurs when a module is partially shaded.
Output Cables
Each module has two standard 90°C rated, water-proof, UV resistant output cables each
terminated with plug & play connectors. This cable is suitable for applications where wiring is
exposed to the direct rays of the Sun.
Field connections
Connecting cables should be a minimum of 12 AWG copper cables, which are UV resistant
and insulated for a minimum of 90°C. All wiring and electrical connections must comply with
local and national Electrical Code.
Blocking Diodes
In a system utilizing a battery, blocking diodes are typically placed between the battery
and the solar module output to prevent battery discharge at night. Diodes that are used as
blocking diodes must: Have a Rated Average Forward Current [IF(AV)] above maximum
system current at highest module operating temperature. Have a Rated Repetitive Peak
Reverse Voltage [VRRM] above maximum system voltage at lowest module operating
temperature.