Installation 16
IDS-509G Hardware Installation Guide
6. Connect P2 (power source 2, beginning at Step 1)
7. Ensure that there is one individual conductor for each clamping point.
Wiring the Relay Alarm
The IDS switch has a relay with a Normally Closed (NC) terminal pair as well as a Nor
-
mally Open (NO) one. Select the connection that suits the application. These terminals are
located on the top panel of the unit. The IDS switch can be connected to an external pow
-
ered device such as a siren or light for visual or audible notification of an alarm status.
1. Ensure the power source is off prior to connection.
2. Strip 2x12-20AWG (3.31 mm² -0.52 mm²) twisted pair copper wires 7-8 mm.
3. Loosen the terminal block screws and connect wires into the terminals.
4. Tighten terminal screws. Ensure the wires are securely fastened.
5. Re-insert the Terminal block connector if removed.
6. Turn on power source.
Warning:
Ensure power has been removed at the source of the alarm circuit prior to pro
-
ceeding with connections to the alarm relay.
Warning:
Ensure the voltage and current supplied by the alarm circuits are within the
stated Alarm Relay specifications.
Warning
: In hazardous location installations, failure to remove the power from the source
prior to completing the wiring connections to the alarm relay could cause an electrical arc
resulting in a possible explosion.
Содержание 07014670
Страница 29: ...Appendix B Sample Labels 27 IDS 509G Hardware Installation Guide Appendix B Sample Labels...
Страница 30: ...Appendix C Mechanical Drawings 28 IDS 509G Hardware Installation Guide Appendix C Mechanical Drawings...
Страница 31: ...Appendix C Mechanical Drawings 29 IDS 509G Hardware Installation Guide...
Страница 32: ...Appendix C Mechanical Drawings 30 IDS 509G Hardware Installation Guide...