. FIELD SETTING
9
. Field setting
9
.1 Outdoor unit DIP switch
Dip Switch Setting of Outdoor Unit
Mark of " " indicates the position of dip switches.
Switch is valid when is ON.
Refrigerant collection function
By default setting is OFF.
OFF ----normal mode
ON----refrigerant collection mode
When the power is ON, the dial changed from OFF to ON, enters into refrigerant collection mode.
During refrigerant recovery mode, system low pressure protect will not occurs, and compressor
will stops after 5 minutes, and will turn to normal state when power on again.
Manual defrost function
By default setting is OFF.
OFF ----normal mode
ON----defrost mode
When the dial changed from OFF to ON in heating mode, enters into defrost mode, and only
valid once.