CT/L-14 Controller
27
•
Protected zone is armed including the selected OD.
•
Passage through the OD (forced entry) sets the system into the “
Alarm
” mode.
11.2 Indication of ACM, events and controller configurations
Connected to the controller remote readers and indication blocks display the indication of ACMs,
states and responses of the controller upon presented identifiers. See Table 4 for possible
indication variants.
Note:
•
When reading an access control card in any operating mode, an audible signal of 0.2
seconds is performed, yellow indicator changes its state for 0.2 seconds. The state of
the other indicators is not changed.
•
After the access is granted, indication is turned on for
Holding in unlocked state
period
or until the passage is performed. When access is denied indication is turned on
for 1 second.
Table 4. Controller indication
Card presentation
ACM
Indicators
Green
Yellow
Red
Sound
Configuration is not selected
No
5 Hz
5 Hz
5 Hz
off
Activation of the
Fire Alarm
input
Any card
1.3/0.2
off
off
off
No
“Open”
on
off
off
off
“Control”
off
on
off
off
“Security”
off
1 Hz
1 Hz
off
“Closed”
off
off
on
off
Card is not authorized for access
“Open”
on
off
off
0.2 sec
“Control”
off
off
on
0.5 sec
“Security”
Any card
“Closed”
Card is authorized for access
“Open”
on
off
off
0.2 sec
“Control”
“Security”
off
off
on
0.5 sec
Card is authorized for access and for
arming/disarming
“Open”
on
off
off
0.2 sec
“Control”
“Security”
Re-presenting a
card with the right
to arming
Change to the
“Security”
mode
“Security”
off
1 Hz
1 Hz
0.2 sec
In case of failure
(before to return to
initial mode)
“Open”
off
off
1 sec
1 sec
“Control”
Waiting for verification
Any
off
2 Hz
off
0.2 sec
1
Blinking (going off briefly) – 1.3 seconds is on, 0.2 seconds is off.
2
In the “
Security
” mode after presentation of access card with the right to disarming the following occurs:
OD disarming and OD unlocking for
Holding in unlocked state period.
After this time expires, the OD
switches to the operating mode set before OD arming (“
Open
” or “
Control
”, if the previous mode was
“
Closed
”, it will switch to the “
Control”
operating mode).
3
Sound and light indication turns on for 1 sec.
Содержание CT/L-14
Страница 1: ...Controller CT L 14 ASSEMBLY AND OPERATION MANUAL...
Страница 2: ...CT L 14 Controller Assembly Operation Manual...