VBA-2A-KE5-IL/UL, VBA-4A-KE5-IJL/UJL
Commissioning
2
0
1
8
-0
7
17
Configuration via Parameters/Jumpers
Jumpers
Parameter
VBA-4A-KE5-IJL/UJL
Output mode
VBA-2A-KE5-IL/UL
Output mode
P1
P3
1
0
1
0
1
1
0
0
4 current outputs
4 voltage outputs
Automatic mode
Reserved
2 current outputs
O1 voltage output/O2
current output
O1 current output/O2
voltage output
2 voltage outputs
x
x
4 voltage outputs
O1 voltage output/O2
current output
x
x
Automatic mode
O1 current output/O2
voltage output
x
x
Reserved
2 voltage outputs
Table 5.1
Configuration of the Output Mode via Parameters/Jumpers
10
12
9
11
CON1
CON2
CON-
CON-
10
12
9
11
CON1
CON2
CON-
CON-
10
12
9
11
CON1
CON2
CON-
CON-
10
12
9
11
CON1
CON2
CON-
CON-
Note!
Never connect the CON1, CON2, and CON- connections with external potentials.
Maximum permissible length of the jumper:
≤
5 cm.