Pepperl+Fuchs VBA-2A-KE5-IL/UL Скачать руководство пользователя страница 15

VBA-2A-KE5-IL/UL, VBA-4A-KE5-IJL/UJL

Commissioning

 2

0

1

8

-0

7

15

5

Commissioning

5.1

Assigning an Address to the Module

To operate the analog output modules in an AS-Interface network, assign a suitable address to 
the AS-Interface slave. The VBP-HH1-V3.0 AS-Interface handheld programming device by 
Fuchs or an AS-Interface master can be used to assign addresses.

VBA-2A-KE5-IL/UL and VBA-4A-KE5-IJL/UJL are standard slaves in line with specification 2.1. 
You can assign addresses 1 ... 31. The default address on delivery is 0.

5.2

Slave Profile

The analog output modules offer the following profile:

The data value is transmitted as defined by AS-Interface profile 7.3.

5.3

Parameterization

The following parameters can be configured: Program the parameters using an AS-Interface 
master, with the VAZ-SW-ACT32 AS-i Control Tools from Fuchs, or with the VBP-
HH1-V3.0 handheld device.

Parameter P0: Watchdog

Default value P0=1, active

Parameter P0 is used to activate the "watchdog" internal monitoring function. The "watchdog" 
function resets the output signals to "0" if communication with the AS-Interface fails.

Parameter P1: Output Mode

Default value P1=1

Parameter P1 is used to select the output mode for the analog outputs. 

VBA-2A-KE5-IL/UL

: Parameter P1 selects current mode or voltage mode for output O1. 

VBA-4A-KE5-IJL/UJL

: Parameter P1 selects current mode or voltage mode for outputs 

O1 ... O4 collectively. 

VBA-2A-KE5-IL/UL

VBA-4A-KE5-IJL/UJL

Profile

= S-7.3.5

S-7.3.6

I/O

= 7

7

ID

= 3

3

ID2

= 5

6

ID1

= F (programmable)

F (programmable)

Note!

Jumpers on CON1 or CON2 override parameter bits P1 and P3.

If you configure the function of the outputs via the parameter bits, ensure that no jumpers are 
installed on CON1 or CON2. See chapter 3.4 and see chapter 3.5.

Содержание VBA-2A-KE5-IL/UL

Страница 1: ...A D Spec 2 1 VBA 2A KE5 IL UL VBA 4A KE5 IJL UJL AS Interface Analog Modules FACTORY AUTOMATION MANUAL...

Страница 2: ...ivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most rece...

Страница 3: ...VBA 2A KE5 IL UL 10 3 5 Configuring the Output Function on the VBA 4A KE5 IJL UJL 11 3 6 Resetting Restarting Automatic Detection 12 4 Installation 13 4 1 Storage and Transport 13 4 2 Unpacking 13 4...

Страница 4: ...4 VBA 2A KE5 IL UL VBA 4A KE5 IJL UJL 7 Appendix A 19 7 1 Value Ranges of the Analog Output Modules 19 7 2 Delay Times 19...

Страница 5: ...if applicable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Respons...

Страница 6: ...re displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This sy...

Страница 7: ...y be operated in altitudes up to 2000 m The ambient temperature range is from 25 C to 70 C The device must be installed in accordance with applicable national laws and regulations If the device is use...

Страница 8: ...utputs can be configured as current outputs 0 mA 20 mA or as voltage outputs 0 V 10 V The module features automatic output detection which allows outputs to be operated as a current or voltage output...

Страница 9: ...inuously illuminated briefly interrupted output in voltage mode Flashing yellow wire break at current output or output value outside of value range Note Behavior of the LEDs LEDs OUT1 OUT4 are continu...

Страница 10: ...N Jumpers to the output configuration ASI ASI AS Interface both ASI terminals and both ASI terminals are bridged in the terminal block AUX AUX Auxiliary voltage both AUX terminals and both AUX termina...

Страница 11: ...nction of the outputs Three configurations are available 4 Current Outputs Default Option Parameter bits P1 1 P3 1 Jumpers 4 Voltage Outputs Parameter bits P1 0 P3 1 10 12 9 11 CON1 CON2 CON CON 10 12...

Страница 12: ...ection can be restarted at any time during operation Switching the supply off and on is not necessary There are two options available 1 Remove the jumper from CON2 and reconnect the jumper to CON 2 Se...

Страница 13: ...erl Fuchs 4 3 Mounting Mount the module by snapping it onto a 35 mm DIN rail Figure 4 1 Unlocking terminals 4 4 AS Interface and AUX Auxiliary Voltage Connection VBA 2A KE5 IL UL and VBA 4A KE5 IJL UJ...

Страница 14: ...ensor supply from external PELV power source EXT Outputs O1 O2 VBA 2A KE5 IL UL Outputs O1 O4 VBA 4A KE5 IJL UJL 2 wire 3 wire 4 wire Connection example or VBA 4A KE5 IJL UJL only L O GND GND S S S S...

Страница 15: ...rface master with the VAZ SW ACT32 AS i Control Tools from Pepperl Fuchs or with the VBP HH1 V3 0 handheld device Parameter P0 Watchdog Default value P0 1 active Parameter P0 is used to activate the w...

Страница 16: ...to VBA 4A KE5 IJL UJL The auxiliary voltage UAUX is not connected This only applies to VBA 2A KE5 IL UL Parameter P3 Output Mode O2 or Automatic Mode Default value P3 1 Parameter P3 is used to select...

Страница 17: ...put O1 current output O2 voltage output 2 voltage outputs x x 4 voltage outputs O1 voltage output O2 current output x x Automatic mode O1 current output O2 voltage output x x Reserved 2 voltage output...

Страница 18: ...ck connection to actuator Actuator with voltage input connected to output in current mode Correct actuator type Correct output mode See chapter 3 4 or see chapter 3 5 and see chapter 5 3 Analog value...

Страница 19: ...1 Conversion Time The conversion time is the time required by the module to convert a digital value into an analog signal The conversion time is 0 7 ms Data sent by master Output signal mA Output LED...

Страница 20: ...the com unit In the profile 7 3 seven frames are required per channel The duration of a cycle depends on the number of occupied addresses in the AS interface network An address is considered occupied...

Страница 21: ...hs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pa...

Отзывы: