Pepperl+Fuchs SIL KFD0-RSH-1 Скачать руководство пользователя страница 12

 2

014-07

12

Safety Manual SIL KFD0-RSH-1(-Y2), KFD2-SL-4

Safety Recommendation

3

Safety Recommendation

3.1

Interfaces

The device has the following interfaces. For corresponding terminals see data 

sheet.

Safety relevant interfaces:

KFD0-RSH-1(-Y2): input, output

KFD2-SL-4: inputs, outputs, common disable input

3.2

Configuration

KFD0-RSH-1(-Y2)

A configuration of the device is not necessary and not possible.

KFD2-SL-4

The device is configurable. The settings do not influence the safety function. For 

further information see data sheet.

3.3

Useful Life Time

Although a constant failure rate is assumed by the probabilistic estimation this 

only applies provided that the useful life time of components is not exceeded. 

Beyond this useful life time, the result of the probabilistic calculation is 

meaningless as the probability of failure significantly increases with time. The 

useful life time is highly dependent on the component itself and its operating 

conditions 

 temperature in particular (for example, the electrolytic capacitors can 

be very sensitive to the working temperature).

This assumption of a constant failure rate is based on the bathtub curve, which 

shows the typical behavior for electronic components.

Therefore it is obvious that failure calculation is only valid for components that 

have this constant domain and that the validity of the calculation is limited to the 

useful life time of each component.

It is assumed that early failures are detected to a huge percentage during the 

installation period and therefore the assumption of a constant failure rate during 

the useful life time is valid.

However, according to IEC 61508-2, a useful life time, based on experience, 

should be assumed. Experience has shown that the useful life time often lies 

within a range period of about 8 ... 12 years.

As noted in DIN EN 61508-2:2011 note NA4, appropriate measures taken by the 

manufacturer and operator can extend the useful lifetime.

Safety Manual SIL KFD0-RSH-1(-Y2), KFD2-SL-4

Содержание SIL KFD0-RSH-1

Страница 1: ...ISO9001 2 3 Relay Module KFD0 RSH 1 Y2 KFD2 SL 4 PROCESS AUTOMATION SAFETY MANUAL SIL...

Страница 2: ...ry for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent v...

Страница 3: ...and Directives 5 2 Planning 6 2 1 System Structure 6 2 2 Assumptions 7 2 3 Safety Function and Safe State 8 2 4 Characteristic Safety Values 9 3 Safety Recommendation 12 3 1 Interfaces 12 3 2 Configu...

Страница 4: ...safety functions can damage property and the environment or cause personal injury for which Pepperl Fuchs GmbH accepts no liability The devices have been developed manufactured and tested according to...

Страница 5: ...uit proofed and overload proofed Line fault detection can be enabled via DIP switch Fault LED and collective error output via Power Rail behave as described within the data sheet of the device 1 3 Man...

Страница 6: ...assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reaction time of the safety system the SFF value...

Страница 7: ...value would then be 10 8 per hour Failure rate based on the Siemens SN29500 data base Failure rates are constant wear out mechanisms are not included External power supply failure rates are not includ...

Страница 8: ...relay outputs need protection by a fuse initiating at 80 of the rated current to avoid contact welding 2 3 Safety Function and Safe State Safety Function KFD0 RSH 1 Y2 Whenever the input of the device...

Страница 9: ...function Output relay in OFF state when input is de energized s 251 6 FIT dd 0 FIT du 0 4 FIT no effect 69 6 FIT total safety function 252 FIT SFF 99 8 MTBF 1 452 years PFH 4 00 x 10 10 1 h PFDavg fo...

Страница 10: ...y in OFF state when input is de energized s 255 FIT dd 0 FIT du 4 4 FIT no effect 72 8 FIT total safety function 259 FIT not part 0 FIT SFF 98 3 MTBF 1 440 years PFH 4 38 x 10 9 1 h PFDavg for Tproof...

Страница 11: ...FMEDA report Device type A Demand mode Low Demand Mode or High Demand Mode Safety function Outputs de energized when common disable input is de energized HFT 0 SIL 2 sd su 324 FIT dd 0 FIT du 1 0 FIT...

Страница 12: ...highly dependent on the component itself and its operating conditions temperature in particular for example the electrolytic capacitors can be very sensitive to the working temperature This assumption...

Страница 13: ...limited by the maximum switching cycles under load conditions You can see the relationship between the maximum switching power and the load conditions in the diagram below Figure 3 1 This is valid for...

Страница 14: ...to define the type of proof test and the interval time period The ancillary equipment required KFD0 RSH 1 Y2 A digital multimeter without special accuracy will be used as ohmmeter mid range recommend...

Страница 15: ...following tables and pictures Test each separate channel that is used in the safety function application and the respective safety path KFD0 RSH 1 Y2 Figure 4 1 Proof test set up for KFD0 RSH 1 The s...

Страница 16: ...een terminals 11 12 load resistor on output Multimeter shows 24 V DC 2 Attach the input voltage subsequently to each input and check that no output is switching For this test the line fault detection...

Страница 17: ...o effect on the safety function not part Probability of failure of components that are not in the safety path total safety function Safety function HFT Hardware Fault Tolerance MTBF Mean Time Between...

Страница 18: ...2014 07 18 Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4 Notes Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4...

Страница 19: ...Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4 Notes 2014 07 19...

Страница 20: ...rl fuchs com PROCESS AUTOMATION PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs represe...

Отзывы: