2
014-07
10
Safety Manual SIL KFD0-RSH-1(-Y2), KFD2-SL-4
Planning
KFD0-RSH-1-Y2
Parameters acc. to IEC 61508
Values
Assessment type and documentation
FMEDA report
Device type
A
Mode of operation
Low Demand Mode or High Demand Mode
HFT
0
SIL
3
Safety function
Output relay in OFF state when input is de-
energized
s
255 FIT
dd
0 FIT
du
4.4 FIT
no effect
72.8 FIT
total (safety function)
259 FIT
not part
0 FIT
SFF
98.3 %
MTBF
1
440 years
PFH
4.38 x 10
-9
1/h
PFD
avg
for T
proof
= 1 year
1.91 x 10
-5
PFD
avg
for T
proof
= 2 years
3.82 x 10
-5
PFD
avg
for T
proof
= 5 years
9.59 x 10
-5
Reaction time
2
< 20 ms
1
acc. to SN29500. This value includes failures which are not part of the safety function.
2
Time between fault detection and fault reaction.
Table 2.2