Installation and Commissioning
The new module has been installed.
Dismounting Modules from the Motherboard
To dismount a module from the motherboard, proceed as follows:
Pull up the red Quick Lok Bars on each side of the module and carefully lift off the entire
module.
The module has been removed from the motherboard.
4.2
Shielding/Grounding
Figure 4.1
Stylized composition of the grounding
The Ethernet cable shields are directly connected to the grounding terminal. We recommend to
connect the grounding terminal to earth in order to achieve the highest protection against
electromagnetic interference (EMI).
If the Ethernet cable leads into a hazardous area, the grounding terminal has to be connected
to protective earth.
It may be necessary to ground all exposed metal parts as a matter of course.
Tip
Earth Connection
Ensure that the grounding practice applied is well-planned and consistent. Ensure a clean
earth at all times.