2015-01
63
Installation VisuNet RM and VisuNet PC
10.4.2
Assembly Instructions for Ex EMC Cable Glands
The supply cables for the Ex e Ethernet and the RS485 or TTY Ex e data interface, the Ex i
keyboard and the Ex i scanner must be shielded, in order to ensure sufficient immunity to
interference (EMC). The cable shields must be connected to the VisuNet RM/PC in
accordance with the assembly instructions below:
Step 1
Strip the cable
Uncover the braiding
Strip the braiding and insulation
staircase-style
With thin cables, the braiding can be
folded back over the insulation jacket
Insert the cable into the gland until the
braiding reaches the contact position
Tighten the gland
Step 2
Insert the cable through the union nut
Insert the cable into the clamping insert
Fold the braiding over the insert
The braiding must overlap the O-ring
by
approx. 2 mm
Step 3
Fit the clamping insert into the
intermediate gland
Assemble the cable gland
That's all!
If the braiding ends in the cable gland