Level Probe LGC2
Diagnostics and Troubleshooting
2017
-0
2
37
8.3
Troubleshooting Specific to HUT Temperature Head Transmitter
Error
Reason
Solution
No measuring
signal
4 to 20 mA cable not connected
correctly.
Connect device, see chapter 6.
No power supplied via the
4 to 20 mA cable.
Check current loop.
Supply voltage too low
(min. 8 V DC).
• Check supply voltage.
• Overall resistance greater than
max. load resistance.
Error current
3.6 mA
or
21 mA
Pt100 resistance thermometer not
connected correctly.
Connect device, see chapter 6.
4 to 20 mA cable not connected
correctly.
Connect device, see chapter 6.
Pt100 resistance thermometer
defective.
Replace the device.
Temperature head transmitter
defective.
Replace the temperature head
transmitter.
Measured value
is inaccurate/
incorrect.
Pt100 resistance thermometer in 2-
wire circuit, cable resistance was
not compensated for.
• Compensate the cable
resistance.
• Connect Pt100 resistance
thermometer as 3-wire or 4-
wire circuit.
Table 8.3