![Pepperl+Fuchs LAL-SRW series Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/pepperl-fuchs/lal-srw-series/lal-srw-series_manual_1527674026.webp)
23
3717
20
11-
05
24 - EN
WARNING DEVICE LAL-SRW
Commissioning
EN
The following table contains a list of possible configuration settings.
Switches
Description
DIP 1
NVF sensor
(NVF-104/34-PF)
ON
connected
OFF
not connected
DIP 2
KVF sensor (KVF-104-PF)
or
SLU sensor (SLU-103-**)
ON
connected
OFF
not connected
DIP 3
Acoustic alarm
ON
Acoustic alarm on.
OFF
Acoustic alarm off.
DIP 4
Relay setting
ON
Relays 1 and 2 switch, irrespective of the alarm states. If
the alarm event is no longer present, relay 1
automatically switches back AND relay 2 remains
unchanged until the alarm is cleared by pressing the
"ALARM RESET" button. It shows that an alarm
occurred.
DIP 5
ON
DIP 4
Relay setting
ON
Relays 1 and 2 switch, irrespective of the alarm states.
After 3 minutes, relay 2 switches again (even if an alarm
status is present). Relay 1 and/or relay 2 are reset when
the sensor no longer has an alarm status. Pressing the
"ALARM RESET" button switches the relays again.
DIP 5
OFF
DIP 4
Relay setting
OFF
In the case of active alarm status, relay 1 switches to
NVF sensor and relay 2 switches to KVF
or
SLU
sensor. Relay 1 and/or relay 2 are reset when the
sensor no longer has an alarm status. Pressing the
"ALARM RESET" button switches the relays again.
DIP 5
ON
DIP 4
Relay setting
OFF
Relays 1 and 2 switch irrespective of the alarm states
and with which sensor. Relay 1 and relay 2 are reset
when the sensor no longer has an alarm status.
Pressing the "ALARM RESET" button switches the
relays again.
DIP 5
OFF
DIP 6
Repeat alarm setting in 24
hours
ON
Repeat alarm on. This also applies to the function of
relays 1 and 2.
OFF
Repeat alarm off.
DIP 7
Reset key (ALARM RESET
activation)
ON
"ALARM RESET" button is activated. The acoustic
alarm and the alarm relay can be reset.
OFF
"ALARM RESET" button is deactivated. The acoustic
alarm and the alarm relay cannot be reset.
DIP 8
Not in use