Mounting and Installation
Mounting and Installing the Device
1.
Observe the safety instructions in the instruction manual.
2.
Observe the information in the manual.
3.
Observe the requirements for the safety loop.
4.
Connect the device only to devices that are suitable for this safety application.
5.
Check the safety function to ensure the expected output behavior.
4.1
Mounting
Tighten the terminal screws with a torque of 0.5 ... 0.6 Nm.
4.2
Configuration
Configuring the Device
The device is configured via DIP switches. The DIP switches are on the side of the device.
1.
De-energize the device before configuring the device.
2.
Remove the device.
3.
Configure the device via the DIP switches.
4.
Secure the DIP switches to prevent unintentional adjustments.
5.
Mount the device.
6.
Connect the device again.
4.2.1
Output Configuration
Note
The device configuration via DIP switches is not safety relevant.
Note
See corresponding datasheets for further information.
Switch
Line fault detection
Internal fault detection
S1
S2
Off
Off
disabled
disabled
On
Off
enabled
disabled
Off
On
not used
On
On
enabled
enabled
Table 4.1