Functional Safety HiD2035, HiD2036
Operation
Proof Test Procedure
1. Put out of service the entire safety loop. Protect the safety application by
means of other measures.
2. Prepare a test set-up, see figures below.
3. Test the devices. Verify the current values as given in table below.
4. Set back the device to the original settings for the application after the test.
HiD2035, HiD2036, 1oo1 Structure
Figure 5.1
Proof test set-up for HiD2035, HiD2036
Channel 2 only for HiD2036
Step No.
Input value (V)
Input value (mA)
Measured input current (mA)
1
6
1.50
1.50
±
0.5
2
14
4.00
4.00
±
0.5
3
14
20.00
20.00
±
0.5
4
22
10.00
10.00
±
0.5
5
22
40.00
40.00
±
0.5
6
30
5.00
5.00
±
0.5
7
30
25.00
25.00
±
0.5
8
30
50.00
50.00
±
0.5
Table 5.1
Steps to be performed for the proof test
HiD2036
SL2
5a
5b
SL1
8a
7a
1a
1b
10a
9a
+
-
1
4
+
-
2
5
11
14
+
-
12
15
+
-
mA
mA
Multimeter
(A)
V
V
1
2
Zone 0, 1, 2
Div. 1, 2