Functional Safety HiD2030(SK)
Planning
3.3
Safety Function and Safe State
Safe State
The safe state depends on the limit value in the respective application.
Safety Function
The device transfers analog signals from the input to the output with a deviation of less
than 2 %.
Values outside the range of the output signals indicate a fault in the periphery or within
the device and a dangerous detected failure. The valid range is
•
3.6 mA to 21 mA for current outputs and
•
0.9 V to 5.25 V for voltage outputs.
DIP switch settings for HiD2030
The outputs can be configured as:
•
4 mA to 20 mA current output
•
1 V to 5 V voltage output
DIP switch settings for HiD2030SK
No user configuration available for this device.
Line Fault Detection
The line fault detection is always active. The line fault detection cannot be deactivated.
Reaction Time
The reaction time for all safety functions is < 10 ms.
Input signals
Output signals
0/4 mA to 20 mA
0/4 mA to 20 mA
0/4 mA to 20 mA
0/1 V to 5 V
Table 3.1
Output
CH 2
CH 1
SW1
SW2
SW3
SW4
4 mA to 20 mA
OFF
OFF
OFF
OFF
1 V to 5 V
ON
ON
ON
ON
Table 3.2
Note
The separate fault bus is not safety relevant.
Note
See corresponding datasheets for further information.