Functional Safety HiC2883

Planning

20

17-

06

13

3.5

Useful Life Time

Although a constant failure rate is assumed by the probabilistic estimation this 

only applies provided that the useful lifetime of components is not exceeded. 

Beyond this useful lifetime, the result of the probabilistic estimation is 

meaningless as the probability of failure significantly increases with time. The 

useful lifetime is highly dependent on the component itself and its operating 

conditions 

 temperature in particular. For example, the electrolytic capacitors 

can be very sensitive to the operating temperature.
This assumption of a constant failure rate is based on the bathtub curve, which 

shows the typical behavior for electronic components.
Therefore it is obvious that failure calculation is only valid for components that 

have this constant domain and that the validity of the calculation is limited to the 

useful lifetime of each component.
It is assumed that early failures are detected to a huge percentage during the 

installation and therefore the assumption of a constant failure rate during the 

useful lifetime is valid.
However, according to IEC/EN 61508-2, a useful lifetime, based on general 

experience, should be assumed. Experience has shown that the useful lifetime 

often lies within a range period of about 8 to 12 years.
As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the 

manufacturer and plant operator can extend the useful lifetime.
Our experience has shown that the useful lifetime of a Fuchs product 

can be higher if the ambient conditions support a long life time, for example if the 

ambient temperature is significantly below 60 

°

C.

Please note that the useful lifetime refers to the (constant) failure rate of the 

device. The effective life time can be higher.

Содержание HiC2883

Страница 1: ...ISO9001 3 Functional Safety Solenoid Driver HiC2883 PROCESS AUTOMATION MANUAL...

Страница 2: ...f Delivery for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most...

Страница 3: ...tandards and Directives for Functional Safety 8 3 Planning 9 3 1 System Structure 9 3 2 Assumptions 10 3 3 Safety Function and Safe State 11 3 4 Characteristic Safety Values 12 3 5 Useful Life Time 13...

Страница 4: ...Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation if applicable EU type e...

Страница 5: ...nderstood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and absolve...

Страница 6: ...splayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol...

Страница 7: ...and de activated The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver The line fault transparency function...

Страница 8: ...ectives System specific standards and directives Functional safety IEC EN 61508 part 1 7 edition 2010 Functional safety of electrical electronic programmable electronic safety related systems manufact...

Страница 9: ...this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reaction time of the safety...

Страница 10: ...ure of 40 C over a long period The humidity level is within manufacturer s rating For a higher average temperature of 60 C the failure rates must be multiplied by a factor of 2 5 based on experience A...

Страница 11: ...afety Function When the input signal is active the output is activated The safe state is introduced when the input voltage is below 5 V DC Reaction Time The reaction time for all safety functions is 1...

Страница 12: ...output is de energized if the input is in low condition s 130 FIT dd 0 FIT du 0 02 FIT total safety function 130 FIT SFF 1 1 No effect failures and Annunciation failures are not influencing the safet...

Страница 13: ...onents that have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component It is assumed that early failures are detected to a huge percentage d...

Страница 14: ...ure the expected output behavior 4 1 Configuration Configuring the Device The device is configured via DIP switches The DIP switches for setting the safety functions are on the side of the device 1 De...

Страница 15: ...haracteristic safety values See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period Check the settings after the configuratio...

Страница 16: ...nput value Output value 1 24 V DC 19 V high On Imax current depends on device version 2 24 V DC 5 V low Off 0 5 mA 3 0 V DC 0 V Off 0 mA Table 5 1 Steps to be performed for the proof test HiC2883 14 1...

Страница 17: ...y loop does not work without the device shut down the application Do not restart the application without taking proper precautions Secure the application against accidental restart 3 Do not repair a d...

Страница 18: ...effect failure is not used for calculation of SFF not part Probability of failure of components that are not in the safety loop total safety function Safety function HFT Hardware Fault Tolerance MTBF...

Страница 19: ...Functional Safety HiC2883 Notes 2017 06 19 Pulscon LTC50 HART...

Страница 20: ...rl fuchs com PROCESS AUTOMATION PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs represe...

Отзывы: