Functional Safety HiC2883
Planning
20
17-
06
11
3.3
Safety Function and Safe State
Safe State
The safe state of the output is the de-energized state. The output current is less
than 0.5 mA.
Safety Function
When the input signal is active, the output is activated. The safe state is
introduced when the input voltage is below 5 V DC.
Reaction Time
The reaction time for all safety functions is < 1 s.
Note!
The fault indication output is not safety relevant.
Note!
The device configuration via DIP switches is not safety relevant.
Note!
See corresponding datasheets for further information.