39
0
2
.05.
2016
CC-Link Gateways
Diagnostics
Safety diagnostics of safe AS-i outputs
The diagnostic informations are transfered via the Input Data Image, coded to the
input bits of the diagnostic address (diagnostic slave) of an AS-i safety slave.
The diagnostics information for the safety output is encoded to the input data of
the diagnostics slave of the respective safety output.
Device colors
The colors refer to the diagnostics in the ASIMON.
Bit value of the input bits of the diagnostic slaves
Bit
AS-i input
E0
diagnostics (see table device colors)
E1
E2
E3
reserved for EDM input
Tab. 8-44. Bit value of input bits of the diagnostic slaves
Value Color
Description
state change
LED "OUT"
1
1.
See documentation of the AS-i slave.
0
green
output on
–
on
1
green
flashing
–
–
–
2
yellow
restart inhibit
auxiliary signal 2
1 Hz
3
yellow
flashing
–
–
–
4
red
output off
–
off
5
red flashing
waiting for reset of error
condition
auxiliary signal 1
8 Hz
6
gray
connection or
internal error
only via Power On
on device
all LEDs
flashing
7
green/yellow
output released,
but not switched on
switched on by setting
the output bit
1
off
Tab. 8-45. Device colors