13
6100 Series Manual
3.3 Technical Data
3.3.1 6100-MP-EX-* Control Unit
General specifications
Operating mode
manual, semi-automatic, or fully automatic - programmable
Series
6100
Number of volume exchanges
4 to 19
Hazardous environment
gas
Supply
Rated voltage U
r
100 ... 250 V AC, 48 ... 62 Hz / 0.2 A
20 ... 30 V DC / 0.6 A
Electrical specifications
Connection
Power
Ex e terminal blocks
Connection
6000-ISB DIN mounted terminal
Input*
Input I
Inputs 1, 2: contact input, 5 V DC at 2 mA
Input type
discrete input, intrinsically safe
Input II
temperature hub, temperature inputs
Input type
intrinsically safe
Sensor type
6000-TEMP-01
Input III
low pressure sensor
Input type
intrinsically safe
Sensor type
EPV-6100-LPP
Input IV
User interface module
Connection
M8 connector, 4-pin (provided)
Input type
intrinsically safe
Output
Output I
AUX 1
Output type
Dry contacts, SPDT
Inrush current
5 A
Contact loading
2 A at 240 V AC resistive load
2 A at 24 V DC
Output II
AUX 2
Output type
Dry contacts, SPDT
Inrush current
5 A
Contact loading
2 A at 240 V AC resistive load
8 A at 24 V DC
Output III
enclosure 1 and 2
Output type
Dry contacts (2) SPST, NO
Inrush current
72 A
Contact loading
8 A at 240 V AC / 120 V AC resistive load
8 A at 24 V DC
Indicators/settings
LED indication
Safe pressure: Blue - safe pressure is achieved
Enclosure power: Green - power on; Red - power off
Rapid exchange: Blue - purging is running
System bypass: Yellow - bypass is activated
Alarm fault: Red (blinking) - any alarm input detected; Red (solid) - fault
Product Description, Technical Data
* Warning:
Inputs 1, 2, 3, and 4 must be used with the SRM-6000 for tested EMC immunity.
Содержание Bebco EPS 6100-MP-EX Series