AS-i 3.0 PROFIBUS Gateway in Stainless Steel
PROFIBUS DP
26
.9.20
1
3
47
The GSD's default user parameter telegram is:
(DP/V1 enabled, diagnostics settings see chap. <Diagnostics>).
user byte 2
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
FD
0
CS
PF
APF
CF
–
default
0
0
0
0
1
1
0
Tab. 10-11.
user byte 3
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
–
0
default
0
0
Tab. 10-12.
LPF:
1: LPF will be transmitted in the diagnostics
0: LPF will not be transmitted
D:
1: Delta list will be transmitted in the diagnostics
0: Delta list will not be transmitted
F:
1: EC-flags will be transmitted in the diagnostics
0: EC-flags will not be transmitted
FD:
If this bit is set, the PROFIBUS diagnostics is refreshed only if the
PROFIBUS norm dictates this ("freeze diagnostics"). In doubt the
data of the PROFIBUS masters diagnostics are not up to date.
CS:
1: ExtDiag will be set if the LCS is not empty
0: ExtDiag will not be set if the LCS is not empty
PF:
1: ExtDiag will be set if there is a periphery fault at the AS-i line
0: ExtDiag will not be set.
APF:
1: ExtDiag will be set if there is an AS-i power fail
0: ExtDiag will not be set.
CF:
1: ExtDiag will be set if there is a configuration error
0: ExtDiag will not be set.
80
16
00
16
00
16
0B
16
06
16
00
16