Pepperl+Fuchs 1001A Series Скачать руководство пользователя страница 7

77

Getting started

Establishing Connection sizes, lengths & Bends

tYpICal sInGlE pRotECtED EnClosURE ConnECtIons

pRotECtED 

EnClosURE

C

B

EnClosURE pRotECtIon VEnt

(Optional)

E

sUpplY

REFEREnCE

1/2" 

pRotECtIVE 

Gas sUpplY 

HEaDER

EnClosURE 

pRotECtIon 

sYstEM

Maximum tubing / pipe length and 

Maximum number of Bends / Elbows

1/4" O.D. Tubing 

Fully Reamed 
Fully Reamed

20 Feet

10 Bends

1/4" O.D. Tubing 

Fully Reamed

Description

tubing or pipe Diameter

Enclosure 

supply

system  

supply tubing

Enclosure 

Reference

1/4" O.D. Tubing 

Fully Reamed

5 Feet

5 Bends

20 Feet

10 Bends

Multi - Enclosure 

Connections 

1/2" I.D. Pipe  

Fully Reamed

10 Feet

5 Elbows

optional Remote 

Venting  

1/2" I.D. Pipe  

Fully Reamed

30 Feet

5 Elbows

a

B

E

D

C

InlEt

EnClosURE 

pRotECtIon 

sYstEM

pRotECtED 

EnClosURE

pRotECtED 

EnClosURE

D

sUpplY

REFEREnCE

InlEt

Connections for Heavier than 

Air Gases and Vapors

oUtlEt

oUtlEt

B

 

tYpICal MUltIplE pRotECtED EnClosURE ConnECtIons

1/2" 

pRotECtIVE 

Gas sUpplY 

HEaDER

a

a

D

C

Connections for Lighter than 

Air Gases and Vapors

HElpFUl HInts

If flammable gases are lighter than air, the inlet con-
nection  to  each  enclosure  must  enter  near  a  bot-
tom corner.  the outlet connection, for an optional 
enclosure  protection  vent  or  piping  to  an  adjacent 
protected enclosure, must exit near an extreme op-
posite top corner.
If flammable gases are heavier than air, inlet and outlet 
connections must be  reversed.
In all cases, the most prevalent gas must determine 
the location of inlet and outlet connections.

Determining Enclosure Inlet & outlet Connection locations

HElpFUl HInts

to  ensure  adequate  protective  gas  flow  to  the  protected  enclosure(s),  all  piping  and  tubing  must  be  fully 
reamed.
precautions must be taken to prevent crimping and other damage to protective gas piping and tubing.

pRotECtED 

EnClosURE

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-6798-Hoffman-A1001YZUMC2-Purging-Pressurization-System-10-CF.aspx

Содержание 1001A Series

Страница 1: ...cessories Supplied with Each Kit Pentair Technical Products 2100 Hoffman Way Anoka Minnesota 55303 PH 763 422 2211 hoffmanonline com Hoffman P N 87571946 Manufactured by 1600 Enterprise Parkway Twinsb...

Страница 2: ...subject to change without notice Table of Contents Page 2 System Purpose and Description Purpose System Description Important Notes Page 3 Identifying Your System Defines specific features of the syst...

Страница 3: ...ion proof differential pressure switch used to detect loss of safe enclosure pressure LPS Less Pressure Switch SYSTEM TYPE Type Z Reduces the internal enclosure area Division rating from Division 2 to...

Страница 4: ...re Warning Nameplate Silkscreened SS Recommended Spare Parts Qty Description Part supercedes 1 Enclosure Pressure Indicator CI 510023 1 Enclosure Pressure Indicator CII 513235 1 Enclosure Pressure Con...

Страница 5: ...Calculation 1 The total volume of all pressurized enclosures devices and wireways must be considered 2 All enclosure device and wireway volumes must be calculated without consideration of internally...

Страница 6: ...SERVICE VALVE SYSTEM SUPPLY FITTING ENCLOSURE PROTECTION SYSTEM SYSTEM MOUNTING BOLT ENCLOSURE SUPPLY TUBING ENCLOSURE PROTECTION VENT optional PROTECTED ENCLOSURE ENCLOSURE CONNECTION FITTINGS ENCLOS...

Страница 7: ...OUTLET OUTLET B TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS 1 2 PROTECTIVE GAS SUPPLY HEADER A A D C Connections for Lighter than Air Gases and Vapors HELPFUL HINTS If flammable gases are lighte...

Страница 8: ...ions are intended for mounting adjacent to the protected enclosure LH RH TM BM configurations are also suitable for 2 schedule 40 pipe mounting In addition these configurations can be accessorized wit...

Страница 9: ...LLED IN LINE FILTER KIT ACCESSORY Provides an 8 5 oz capacity 40 micron protective gas supply filter factory installed on the inlet side of the enclosure pressure control regulator Typical Surface Mou...

Страница 10: ...10 10 Mounting Plate Dimensions Model 1001A Face Plate 9 8 9 8 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 11: ...25 TYP 4 Flange Depth 6 3 375 1 1 0 675 0 5 Universal Flange Footprint Optional Wall Flange Footprint only available from Pepperl Fuchs RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply c...

Страница 12: ...cted enclosure The length of time required is determined by the customer and can be factory or field engraved All EWNs and ETWs are furnished with an adhesive back but should also be riveted or screwe...

Страница 13: ...odel ILFK accessory See photo on page 9 One 1 Similar fitting which will connect the inert gas supply tubing to the inert gas supply header connection point and one 1 lot of 1 4 O D 035 wall thickness...

Страница 14: ...closure protection system whenever possible For systems protecting multiple enclosures in series the enclosure reference connection fitting must be placed on the last enclosure in the series see page...

Страница 15: ...nections are bolded System Supply Venturi Orifice Inlet Enclosure Pressure Gauge Regulator Sintered Vent Reference Supply Enclosure Reference Bulkhead fitting Enclosure Supply Bulkhead fitting System...

Страница 16: ...or 500 3 as required and all relevant plant and local codes Note Do not use seals on conduit used as a protected wireway to supply protective gas to adjacent protected enclosures The same conduit can...

Страница 17: ...ocked position upon arrival To adjust regulator pull handle to outward position 1 Close the Enclosure Pressure Control Regulator fully by turning counterclockwise CCW 2 Temporarily connect the inert g...

Страница 18: ...ed if utilized 1 Carefully read Start Up Instruction Nameplate on system 2 CheckoperationoftheEnclosureProtectionVent EPV 1 if utilized opening it manually several times see page 17 Helpful Hint 3 Sea...

Страница 19: ...osure Remove the orifice cut off the crimped end and ream the tube then recrimp and reinstall the tube to note effect As tube is shortened reamed andrecrimped sensitivitydecreases allowingeasieradjust...

Страница 20: ...O THE PRODUCTS IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT P F MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE EXCEPT FOR THE LIMITED WARRANTY SET FORTH HEREIN THERE IS NO OTHE...

Страница 21: ...ing to the set up procedure and operating sequence on pages 17 and 18 Replace or tighten stem packing nut as required to prohibit stem packing leakage Carefully disassemble the enclosure protection ve...

Страница 22: ...22 22 CUSTOMER NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 23: ...23 23 CUSTOMER NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 24: ...omer Project Service Type Features Application SYSTEMS IDENTIFICATION APPLICATION INFORMATION Local Sales Representative NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798...

Отзывы: