Electrical supply Requirements

Explosion

Proof Device

typical Enclosure Wiring Methods

Protected  enclosures  must  be  wired  similar  to  explosion 
proof enclosures, in accordance with 

article 501-504

 of the 

1999 National Electric Code - 

nFpa 70

Single conductor wiring must be placed in rigid metal conduit, 
seal-flex conduit or other mediums approved for use in the 
hazardous  location  surrounding  the  protected  enclosure.  
Although  the  1998  edition  of  NFPA  496  does  not  require 
conduit seals on pressurized enclosures in a division 2 area, 
Fuchs strongly recommends the use of a conduit 
seal as  the most practical way to prevent excessive leakage 
through conduit connections. 

While explosion proof enclosures require conduit seals on 
all  cable  entries,  in  accordance  with 

nFpa  70

sections 

501-5

, protected enclosure cable entries can be sealed in 

accordance with 

section 501-5

 which permits the use of 

compression gland fittings or other sealed cable entry fittings, 
as opposed to approved conduit seals, if the wiring method 
is otherwise suitable for the hazardous location.

In conclusion, there are two primary goals.  First, the installer 
should ensure all associated wiring and cable is protected 
by pressurization or other means, such as explosion proof 
conduit or intrinsic safety barriers.  Secondly, the installer 
must ensure all associated conduit and wireways are sealed 
to conserve protective gas, unless they are used to supply 
protective gas to other enclosures or devices.

typical Enclosure Wiring Connections

Seal

Intrinsically

Safe Or Fiber

Optic Device

Adjacent

Pressurized

Device

Independently

Pressurized

Device

Intrinsically

Safe Or Fiber

Optic Device

Seal

Conduit

Conduit

Conduit

General Wiring Requirements

WaRnInG

tHIs DEVICE ContaIns ElECtRICal paRts WHICH 

Can CaUsE sHoCK oR InJURY

All electrical connections, conduit and fittings on the protected 
enclosure must be suitable for the hazardous location in which 
they are installed.  In addition, all conduit and wire must be 
installed in accordance with NEC articles 500-1, 500-2 or 
500-3 as required and all relevant plant and local codes. 

note: 

  Do  not  use  seals  on  conduit  used  as  a  protected 

“wireway” to supply protective gas to adjacent protected 
enclosures.    The  same  conduit  can  be  utilized  for  both 
electrical and pneumatic service to an adjacent protected 
enclosure(s), provided the conduit is oversized to allow a 
minimum free clearance equal to or larger than the pipe size 
required between multiple enclosures as stated on page 7, 
“Getting Started”.

Enclosure power Requirements

The  protected  enclosure(s)  electrical  power  source  must 
originate  from  a  circuit  breaker  or  fused  disconnect  suit-
able for the hazardous location in which it is installed.   The 
switch must be located within fifty (50) feet of the protected  
enclosure(s) and the protection system and be properly marked.

alarm signal Requirements

The protected enclosure(s) alarm signal may originate from 
the protected enclosure if the alarm signal is disconnected by 
the protected enclosure's circuit breaker or fused disconnect 
as stated in Enclosure Power Requirements above.

The  protected  enclosure(s)  alarm  signal  power  may  also 
originate from outside of the protected enclosure.  In this 
application,  the  protected  enclosure  may  be  used  as  a 
“wireway” to pass alarm signal wiring from the power source 
to  the  alarm  device,  if  the  wiring  is  isolated  and  properly 
labeled.    In  addition,  appropriate  conduit  seals  must  be 
provided  outside  of  the  protected  enclosure  separately. 

IMpoRtant notE 

nFpa 496 requires the use of an alarm or an indicator to 
detect the loss of safe enclosure pressure.  In addition, 
the  nFpa  496  requires  that  if  an  indicator  alone  is 
utilized, a protective gas supply alarm must also be 
installed between the last valve in the protective gas 
supply and the protected enclosure.  therefore, the 
protective gas supply to all lps style systems must 
be  equipped  with  the  above  mentioned  protective 
gas  supply  alarm.    Exception:  systems  utilizing  an 
EpsK or GpsK enclosure pressure loss alarm switch 
accessory  will  satisfy  the  above  mentioned  nFpa 
requirement.

Gland

Fitting

Cable

Seal

Pressurized

Raceway

Protected Enclosure

Or Device

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-6798-Hoffman-A1001YZUMC2-Purging-Pressurization-System-10-CF.aspx

Содержание 1001A Series

Страница 1: ...cessories Supplied with Each Kit Pentair Technical Products 2100 Hoffman Way Anoka Minnesota 55303 PH 763 422 2211 hoffmanonline com Hoffman P N 87571946 Manufactured by 1600 Enterprise Parkway Twinsb...

Страница 2: ...subject to change without notice Table of Contents Page 2 System Purpose and Description Purpose System Description Important Notes Page 3 Identifying Your System Defines specific features of the syst...

Страница 3: ...ion proof differential pressure switch used to detect loss of safe enclosure pressure LPS Less Pressure Switch SYSTEM TYPE Type Z Reduces the internal enclosure area Division rating from Division 2 to...

Страница 4: ...re Warning Nameplate Silkscreened SS Recommended Spare Parts Qty Description Part supercedes 1 Enclosure Pressure Indicator CI 510023 1 Enclosure Pressure Indicator CII 513235 1 Enclosure Pressure Con...

Страница 5: ...Calculation 1 The total volume of all pressurized enclosures devices and wireways must be considered 2 All enclosure device and wireway volumes must be calculated without consideration of internally...

Страница 6: ...SERVICE VALVE SYSTEM SUPPLY FITTING ENCLOSURE PROTECTION SYSTEM SYSTEM MOUNTING BOLT ENCLOSURE SUPPLY TUBING ENCLOSURE PROTECTION VENT optional PROTECTED ENCLOSURE ENCLOSURE CONNECTION FITTINGS ENCLOS...

Страница 7: ...OUTLET OUTLET B TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS 1 2 PROTECTIVE GAS SUPPLY HEADER A A D C Connections for Lighter than Air Gases and Vapors HELPFUL HINTS If flammable gases are lighte...

Страница 8: ...ions are intended for mounting adjacent to the protected enclosure LH RH TM BM configurations are also suitable for 2 schedule 40 pipe mounting In addition these configurations can be accessorized wit...

Страница 9: ...LLED IN LINE FILTER KIT ACCESSORY Provides an 8 5 oz capacity 40 micron protective gas supply filter factory installed on the inlet side of the enclosure pressure control regulator Typical Surface Mou...

Страница 10: ...10 10 Mounting Plate Dimensions Model 1001A Face Plate 9 8 9 8 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 11: ...25 TYP 4 Flange Depth 6 3 375 1 1 0 675 0 5 Universal Flange Footprint Optional Wall Flange Footprint only available from Pepperl Fuchs RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply c...

Страница 12: ...cted enclosure The length of time required is determined by the customer and can be factory or field engraved All EWNs and ETWs are furnished with an adhesive back but should also be riveted or screwe...

Страница 13: ...odel ILFK accessory See photo on page 9 One 1 Similar fitting which will connect the inert gas supply tubing to the inert gas supply header connection point and one 1 lot of 1 4 O D 035 wall thickness...

Страница 14: ...closure protection system whenever possible For systems protecting multiple enclosures in series the enclosure reference connection fitting must be placed on the last enclosure in the series see page...

Страница 15: ...nections are bolded System Supply Venturi Orifice Inlet Enclosure Pressure Gauge Regulator Sintered Vent Reference Supply Enclosure Reference Bulkhead fitting Enclosure Supply Bulkhead fitting System...

Страница 16: ...or 500 3 as required and all relevant plant and local codes Note Do not use seals on conduit used as a protected wireway to supply protective gas to adjacent protected enclosures The same conduit can...

Страница 17: ...ocked position upon arrival To adjust regulator pull handle to outward position 1 Close the Enclosure Pressure Control Regulator fully by turning counterclockwise CCW 2 Temporarily connect the inert g...

Страница 18: ...ed if utilized 1 Carefully read Start Up Instruction Nameplate on system 2 CheckoperationoftheEnclosureProtectionVent EPV 1 if utilized opening it manually several times see page 17 Helpful Hint 3 Sea...

Страница 19: ...osure Remove the orifice cut off the crimped end and ream the tube then recrimp and reinstall the tube to note effect As tube is shortened reamed andrecrimped sensitivitydecreases allowingeasieradjust...

Страница 20: ...O THE PRODUCTS IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT P F MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE EXCEPT FOR THE LIMITED WARRANTY SET FORTH HEREIN THERE IS NO OTHE...

Страница 21: ...ing to the set up procedure and operating sequence on pages 17 and 18 Replace or tighten stem packing nut as required to prohibit stem packing leakage Carefully disassemble the enclosure protection ve...

Страница 22: ...22 22 CUSTOMER NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 23: ...23 23 CUSTOMER NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798 Hoffman A1001YZUMC2 Purging Pressurization System 10 CF aspx...

Страница 24: ...omer Project Service Type Features Application SYSTEMS IDENTIFICATION APPLICATION INFORMATION Local Sales Representative NOTES RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 6798...

Отзывы: