Functional Safety KFD0-CS-(Ex)*.54*, KFD0-CS-(Ex)*.56*

Planning

201

8-06

13

3.5

Useful Lifetime

Although a constant failure rate is assumed by the probabilistic estimation this only applies 

provided that the useful lifetime of components is not exceeded. Beyond this useful lifetime, 

the result of the probabilistic estimation is meaningless as the probability of failure significantly 

increases with time. The useful lifetime is highly dependent on the component itself and 

its operating conditions 

 temperature in particular. For example, the electrolytic capacitors 

can be very sensitive to the operating temperature.

This assumption of a constant failure rate is based on the bathtub curve, which shows 

the typical behavior for electronic components.

Therefore it is obvious that failure calculation is only valid for components that have 

this constant domain and that the validity of the calculation is limited to the useful lifetime 

of each component.

It is assumed that early failures are detected to a huge percentage during the installation and 

therefore the assumption of a constant failure rate during the useful lifetime is valid.

However, according to IEC/EN 61508-2, a useful lifetime, based on general experience, 

should be assumed. Experience has shown that the useful lifetime often lies within a range 

period of about 8 to 12 years.

As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer 

and plant operator can extend the useful lifetime.

Our experience has shown that the useful lifetime of a Fuchs product can be higher 

if the ambient conditions support a long life time, for example if the ambient temperature is 

significantly below 60

°

C.

Please note that the useful lifetime refers to the (constant) failure rate of the device. 

The effective life time can be higher.

Содержание 072221

Страница 1: ...ISO9001 2 Functional Safety Repeater KFD0 CS Ex 54 KFD0 CS Ex 56 PROCESS AUTOMATION MANUAL...

Страница 2: ...for Products and Services of the Electrical Industry published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent ver...

Страница 3: ...2 1 Function 7 2 2 Interfaces 7 2 3 Marking 8 2 4 Relevant Standards and Directives 8 3 Planning 9 3 1 System Structure 9 3 2 Assumptions 10 3 3 Safety Function and Safe State 11 3 4 Characteristic S...

Страница 4: ...leshooting Dismounting Disposal The documentation consists of the following parts Present document Instruction manual Manual Datasheet Additionally the following parts may belong to the documentation...

Страница 5: ...read and understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty an...

Страница 6: ...ges are displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger Th...

Страница 7: ...monitored by control systems Additionally the device transfers AC signals from the field device to the control system This transfer can be used as safety relevant information channel for an alarm syst...

Страница 8: ...nnheim Germany Internet www pepperl fuchs com KFD0 CS Ex1 54 KFD0 CS Ex1 54 Y KFD0 CS Ex2 54 KFD0 CS Ex1 56 KFD0 CS Ex2 56 Up to SIL 2 KFD0 CS Ex1 54 Y72221 Part number 072221 KFD0 CS Ex1 54 Part numb...

Страница 9: ...lly the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault reac...

Страница 10: ...solver is designed such that all currents below 1 mA or above 40 mA 20 mA for KFD0 CS Ex 54 are detected and lead to the safe state SIL 2 Application The device shall claim less than 10 of the total f...

Страница 11: ...the alarm state Analog current signal transfer Enough voltage is available to supply the connected alarm devices while communication is not relied on Safe State Safety relevant communication The alarm...

Страница 12: ...on Safety relevant communication Analog current signal transfer s 60 FIT 0 FIT dd 0 FIT 34 0 FIT du 5 7 FIT 34 2 FIT total safety function 132 FIT 68 FIT no effect 66 FIT 58 FIT not part 16 0 FIT 22 2...

Страница 13: ...d for components that have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component It is assumed that early failures are detected to a huge pe...

Страница 14: ...fety instructions in the instruction manual 2 Observe the information in the manual 3 Observe the requirements for the safety loop 4 Connect the device only to devices that are suitable for this safet...

Страница 15: ...oof test can be performed which will reveal all of the possible dangerous faults diagnostic coverage 100 Equipment required Digital multimeter with an accuracy better than 0 1 Use for the proof test o...

Страница 16: ...voltage V 54 Y2 versions Output voltage V 54 Y3 versions Output voltage V 56 versions 1 24 00 0 00 22 75 0 75 22 75 0 75 22 75 0 75 n a 2 24 00 4 00 21 00 0 50 20 00 0 30 21 50 0 50 n a 3 24 00 20 00...

Страница 17: ...r replaced If the safety loop does not work without the device shut down the application Do not restart the application without taking proper precautions Secure the application against accidental rest...

Страница 18: ...not used for calculation of SFF not part Probability of failure of components that are not in the safety loop total safety function Probability of failure of components that are in the safety loop HF...

Страница 19: ...Functional Safety KFD0 CS Ex 54 KFD0 CS Ex 56 Notes 2018 06 19...

Страница 20: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Отзывы: