background image

THERMAL MANAGEMENT SOLUTIONS

EN-TraceTekTTDM128-IM-H57341      03/13

4 / 6

connect the alarm relays.

The TTDM-128 has three relays, for service 

ck

, leak 

bt

, and fault 

bs

. Each relay provides two Form-C relay contacts, and normally 

open and normally closed contacts are both provided. The relays 

are 

de-energized to indicate an alarm

 condition. The illustration 

shows the relay status in the alarm (de-energized) state.

The illustrations that follow show how relays can be jumpered 

together to allow remote monitoring of the TTDM-128 status with 

only a single pair of wires. The TTDM-128 

de-energizes

 its relays 

to signal an alarm condition. Therefore, loss of power, as well as 

any other type of alarm, would signal the remote alarm.

Note: 

The relay plugs can accept wires 10 AWG (4.7 sq. mm) or 

smaller. We recommend 18 AWG (1.0 sq. mm) wires. Cable should 

have a  temperature rating of 65°C.

Note:

 Maximum load for relays is 5 A.

LEAK RELAY

SERVICE RELAY

FAULT RELAY







Monitoring circuit

(alarm on open circuit)

Relays wired

in series

Alarm on open circuit

Monitoring circuit

(alarm on closed circuit)

Relays wired

in parallel

Alarm on closed circuit













Test after supplying power.

• Close and latch the enclosure door.
• Supply power to the unit. When power is supplied, the green LED 

illuminates, and the unit goes through a series of self-tests. Af-

ter the start-up sequence is complete, the module should report 

a fault alarm (this is normal; there is no sensing cable attached). 

Press the red Silence key to silence the audible alarm. Verify that 

the display appears similar to the one shown here (the time and 

date may be different):

  If anything other than the above occurs, check all connections. If 

unit still does not appear to operate properly, contact a TraceTek 

representative for assistance.

• Press the Test button. The module conducts a number of self-tests.

• If the tests are successfully completed, record this on the instal

-

lation record.

• Turn off the power supply to the unit.

Test with TTdM-128 test plug.

• To conduct a more complete test, use the TraceTek TTDM-CTP test 

plug (packed in a plastic bag in the TTDM packaging). Insert the plug 

into the sensing cable socket 

cn

 on the sensor interface board 

9

.

• Close and latch the enclosure door.
• Supply power to the unit. When power is supplied, the unit will again 

go through a series of self-tests. If the test plug is in the sensing cable 

socket, after the module completes the start-up sequence it should 

sound and display a leak alarm. Press the Silence key to silence the 

audible alarm. The red Leak LED and green Monitoring LED should 

both be illuminated, and the screen display should appear similar to 

the one shown here (depending on the setting).

• If anything other than the above occurs, check all connections. If unit 

still does not appear to operate properly, contact a TraceTek represen-

tative for assistance.

• If the test is successfully completed, record this on the installation 

record.

• Turn off the power supply to the unit.
• Remove the TTDM-CTP test plug and store it in a secure place for 

future use.

• If not immediately connecting the sensing cable, or TraceTek net

-

work, close and latch the enclosure.

Depending on the units selected, the leak 

distance should be within the values below:

feet: 

527 to 548 ft

meters:  160 to 168

zones:  11

Testing the Module

Отзывы: