THERMAL MANAGEMENT SOLUTIONS
EN-TraceTekTTDM128-IM-H57341 03/13
2 / 6
1
LCD display
2
LEDs with icons
3
Test key
4
Silence key
5
Reset key
6
Menu keys
7
User Interface board
8
4—20 mA board (optional)
9
Sensor Interface board
bk
Motherboard
bl
Power supply board
bm
Fuse (500 mA, 250 V, time delay)
bn
Power cable plug and socket
bo
Voltage Selector Switch
bp
Spare fuse
bq
Ground/earth stud
br
Gland plate
bs
Fault relay cable plug and socket
bt
Leak relay cable plug and socket
ck
Service relay cable plug and socket
cl
4—20 mA port plug and socket
cm
RS-232/485 host port plug and
socket
cn
Sensing cable plug and socket
co
RS-485 TraceTek Network Plug
& Socket
cp
Ribbon cable
cq
Host port RS-232/485 selector
cr
9 pin RS-232 socket
cs
Reset pins
ct
Volume adjustment
dk
LCD contrast adjustment
pL
indicates power limited circuits
Note
: To avoid damage to the unit, store the TTDM-128 module in
its cardboard box until construction is complete.
Select the mounting position.
Choose a location indoors where the module will be protected
from the elements and temperature extremes.
• Remove the module from its carton. Do not remove the
protective film from the membrane on the front of the unit.
• Open the enclosure door using a flat-blade screwdriver or a coin.
Important:
The TTDM-128 is an electronic unit. During instal-
lation, take the following precautions to avoid damage to its
electronic components:
• Handle with care, avoid mechanical damage.
• Keep the electronics dry.
• If handling circuit boards, hold them by their edges to avoid
physical contact with electronic components.
• Avoid exposure to static electricity.
• Avoid contamination with metal filings, liquids, or other foreign
matter.
WARNING: Ignition hazard. do not mount the TTdM-
128 unit in a hazardous location. Sensing cable
connected to the TTdM-128 may (subject to
approvals restrictions) be located in hazardous
locations, but the module itself must be in an
ordinary area.
Note:
The TraceTek sensing circuit is power limited, so the
TraceTek leader or jumper cable and the power supply
cable must not run in the same conduit.
Installing the TTdM-128