Knob Stopper

Screw A

OPERATING (CONTROLS)

Dual Temperature Control System - 

(Electronic and Millivolt Models)

Operation (contd.)

For convenience and economy all MiniMax Plus heaters
are equipped with two thermostats on the front of the heater
control panel; see Figure 7.

Figure 7.

Figure 8.

THERMOSTAT KNOB STOPPER

Each thermostat is equipped with a mechanical stop that
can be locked or unlocked with use of a screwdriver to
prevent temperatures in excess of that desired by the user;
see Figure 8.

The maximum setting can be adjusted by loosening the screw
"A" and turning the stopper dial to desired maximum setting.
Lock the setting by tightening the screw. The Mechanical
stop is under the knob. Ensure that the knob is stopping at the
correct position when the knob is rotated clockwise from a
lower temperature position. (See Thermostat Adjustment.)

NOTE

To eliminate error due to piping heat losses,
measure pool temperature with an accurate
thermometer directly at the pool or spa.

THERMOSTAT ADJUSTMENT

The knob with locking feature eliminates the need for
constant thermostat adjustments. Set the knob pointer to
the desired pool or spa temperature.
If further adjustment is needed, rotate the knob until the
desired temperature is obtained. This knob position
corresponding to your desired maximum pool or spa
temperature may now be preset (locked) by the knob
stopper which prevents the knob from being turned beyond
the maximum temperature you set.

POWER (THERMOSTAT SELECT) SWITCH

The Pool/Off/Spa switch allows the heater to be turned off
when heating is not desired.

1.

“Pool” position - Maintains selected pool
temperature.

2.

“Off” position - Heater will not come on regardless
of drop in pool or spa temperature.

3.

“Spa” position - This allows separate control of spa
water temperature.

INDICATOR LIGHT DESCRIPTION

The MiniMax Pool Heater provides nine status indicator lights, six can be seen from the front of the control panel which
help you understand the operation of the heater. If something should go wrong, the lights will aid in troubleshooting the
problem. Three additional lights can be seen after opening the control panel. These three lights give the service technician
advanced troubleshooting capability. All the LED lights are green with the exception of the red service LED.

POWER LIGHT (POWER)

The light is on at all times, in any switch position, indicating
24 VAC power is being supplied to the control circuit. If it
fails to light, no other light will be on. Possible causes are:
a) external power to the heater is disconnected, check
service panel circuit breaker or fuses; b) local circuit
breaker inside the transformer has tripped -- investigate
cause before resetting; c) transformer has failed.

THERMOSTAT (TSTAT)

This light is on when the thermostat contacts close, signaled
by the water temperature falling below the setpoint, calling
for the heater to fire to maintain the desired water
temperature.

AUXILIARY (AUX)

This light is on when it indicates the remote switch contacts
are closed. This allows you to observe if your remote switch
is properly closing the heater control circuit. When shipped
from the factory a jumper is installed to maintain closed
circuit in the absence of a remote switch.

PRESSURE (PRESS)

This light is on when Spa/Pool Selector switch is on,
indicates the circulation pump is running properly. If
pressure light fails to light, the pump may have lost its
prime or water flow may be restricted by an inadvertently
closed valve or clogged filter or pump basket. If you have
determined that there is no water flow restriction to the
heater, you should call a qualified serviceman.

Содержание spa heater

Страница 1: ...th Installation and service must be performed by a qualified installer service agency or the gas supplier MiniMax Plus and PowerMax POOL SPA HEATERS OPERATION INSTALLATION MANUAL WARNING WHAT TO DO IF...

Страница 2: ...ections 14 Reverse Water Connections 14 Plumbing Plumbing Connections 14 Manual Bypass 14 Below Pool Installation 14 Quick Flange Installation 15 Gas Connections 16 Gas Line Installation 16 Pipe Sizin...

Страница 3: ...Rev E 2 7 01 P N 471048 3...

Страница 4: ...r temperature with an accurate thermometer Spa or hot tub thermostats may err in regulating water temperatures by as much as 4 F 2 2 C 5 Persons with a medical history of heart disease circulatory pro...

Страница 5: ...RATION NATURAL GAS 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device which a...

Страница 6: ...y information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device which automatically lights the pilot Do not try...

Страница 7: ...T FORCE 5 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety informa tion above If you don t smell gas go to the next step 6 Push in gas control knob slightly a...

Страница 8: ...temperature 3 Spa position This allows separate control of spa water temperature INDICATOR LIGHT DESCRIPTION The MiniMax Pool Heater provides nine status indicator lights six can be seen from the fro...

Страница 9: ...Rev E 2 7 01 P N 471048 9...

Страница 10: ...P N 471048 Rev E 2 7 01 10...

Страница 11: ...ols that are only used on the weekends it is not necessary to leave the thermostat set at 78 F Lower the temperature to a range that can be achieved easily in one day Generally this would be 10 F to 1...

Страница 12: ...ble pH range It is essential to maintain correct pH see Table 2 If pH becomes too high over alkaline it has these effects 1 Greatly lowers the ability of chlorine to destroy bacteria and algae 2 Water...

Страница 13: ...ation of this type of heating equipment and related components Some states require installation and repair by licensed personnel If this applies in your state be sure your contractor bears the appropr...

Страница 14: ...tant 3 Disconnect the pressure switch wiring 4 Remove the temperature sensing bulb from the in out header Note You may cut the wire bundle ties 5 Exchange the in out header with the return header Rep...

Страница 15: ...break up any grease or contaminant that may not be cleaned away with a primer 5 Use 711 PVC glue or equivalent and follow the manufacturer s recommendations Apply to the inlet opening of the Quick Fla...

Страница 16: ...be leak tested before placing the heater in operation Do not use flame to test the gas line Use soapy water or another nonflammable method A manual main shut off valve must be installed externally to...

Страница 17: ...use of a stack type outdoor vent kit available at additional cost NOTE This unit shall not be operated outdoors at temperatures below 0o F for propane and 20o F for natural gas Figure 20 Figure 19 l e...

Страница 18: ...employed in every indoor installation with the exception of the PowerMax units The heater must be located as close as practical to a chimney or gas vent The heater should be installed at least 5 feet...

Страница 19: ...6 4 n i 7 0 0 3 0 3 H D 1 3 2 0 6 4 n i 8 0 5 3 5 3 H D 3 3 2 0 6 4 n i 9 0 0 4 0 4 H D 4 3 2 0 6 4 n i 0 1 Table 13 e d i s n I m o r F r i A l l A l e d o M n o i t s u b m o C r o f r i A n I q S...

Страница 20: ...E If any of the original wiring supplied with this heater must be replaced installer must supply No 18 AWG 105 C U L approved AWM low energy stranded copper wire or it s equivalent In Canada wires mus...

Страница 21: ...CLOSE ON CALL FOR HEAT POOL OFF SPA THERMOSTAT SELECT SWITCH TEMPERATURE PROBE GND MV IGNITION MODULE SPARK IGNITER IGNITION WIRE RED BLU WHT THERMAL FUSE RED RED WHT WHT PV ORG P4 P7 PI0 P11 J4 J7 J...

Страница 22: ...F TH PP TH PP POT 1 THERMOSTAT BOARD POT 2 TH PP PP POT SENSOR SEN TH WHT IF ORIGINAL FACTORY WIRING MUST BE REPLACED INSTALLER MUST SUPPLY UL OR CSA IF CANADA APPROVED WIRE 18 GAUGE 600V 105 C TEMPER...

Страница 23: ...tch to ON Heater Short Cycling Rapid On and Off Operation Insufficient water flow Clean filter and pump strainer Defective wiring Repair or replace wiring Defective flow valve or out of adjustment Cal...

Страница 24: ...P N 471048 Rev E 2 7 01 24 MINIMAX PLUS HEATER ALL MODELS...

Страница 25: ...7 0 8 9 9 3 7 0 8 9 9 3 7 0 D I I e n a p o r p e v l a v s a G 1 9 9 9 3 7 0 9 9 9 3 7 0 9 9 9 3 7 0 9 9 9 3 7 0 9 9 9 3 7 0 9 9 9 3 7 0 t l o v i l l i M l a r u t a n e v l a v s a G 1 7 5 4 5 7 0...

Страница 26: ...8 9 6 1 7 0 8 9 6 1 7 0 8 9 6 1 7 0 8 9 6 1 7 0 8 9 6 1 7 0 4 1 x 6 w e r c S 6 1 7 1 7 0 6 1 7 1 7 0 6 1 7 1 7 0 6 1 7 1 7 0 6 1 7 1 7 0 6 1 7 1 7 0 4 1 x 2 3 0 1 w e r c S 9 5 6 1 7 0 9 5 6 1 7 0 9...

Страница 27: ...Rev E 2 7 01 P N 471048 27...

Страница 28: ...stalled and or operated Be sure to follow the instructions set forth in this manual CODE REQUIREMENTS The installation must conform with local codes or in the absence of local codes with the latest na...

Страница 29: ...ure switch is in the ignition module circuit and the ignition module does not operate unless the switch is closed Figure 2 DESCRIPTION OF SYSTEM OPERATION SYSTEM OPERATION 1 Set the thermostat to the...

Страница 30: ...P N 471048 Rev E 2 7 01 30 30...

Страница 31: ...above public walkways must be at least 3 ft above any outside air intake located within a 10 ft radius must NOT be within 3 ft of an inside corner of the structure must be at least 1 ft above grade mu...

Страница 32: ...a horizontal stack Optional Horizontal Venting Must be the same diameter as the vent connector Must be suitable for use with Category III Appliances which have flue gas temperatures of less than 400...

Страница 33: ...CUIT BOARD SPST EXTERNAL ON OFF SWITCH HIGH LIMIT THERMAL SWITCHES WATER PRESSURE SWITCH JUMPER REQUIRED IF NO REMOTE SWITCH CONTROL RELAY CLOSE ON CALL FOR HEAT POOL OFF SPA THERMOSTAT SELECT SWITCH...

Страница 34: ...24V and connect it to the orange wire from the air pressure switch 3 Connect the blue wire from the air pressure switch to the ignition module pin 6 24V 4 The green wire that comes from the relay con...

Страница 35: ...O THERMOSTAT CIRCUIT BOAD ORANGE TAB 24V TAB MALE ORANGE BLUE 24 VAC RELAY WHITE COMMON GREEN SAFETY GROUND GREEN MOTOR FAN HEATER GROUND LUG BLACK 120 VAC ONLY HOT AIR PRESSURE BLACK BLACK SWITCH ORA...

Страница 36: ...P N 471048 Rev E 2 7 01 36 A 10...

Страница 37: ...C 1 9 3 0 1 7 4 0 4 0 1 7 4 1 4 0 1 7 4 2 4 0 1 7 4 3 4 0 1 7 4 4 4 0 1 7 4 5 1 y s s a r o o D 1 8 6 4 5 7 0 4 0 6 5 7 0 8 8 4 5 7 0 5 0 6 5 7 0 6 0 6 5 7 0 0 9 4 5 7 0 6 1 r e n r u b d l o f i n a...

Страница 38: ...3 n a x e L t u o n i g n i h s u B 2 4 4 5 0 7 0 4 4 5 0 7 0 4 4 5 0 7 0 4 4 5 0 7 0 4 4 5 0 7 0 4 4 5 0 7 0 2 3 2 t u o n i r e b b u r e v e e l S 2 5 9 8 1 7 0 5 9 8 1 7 0 5 9 8 1 7 0 5 9 8 1 7 0...

Страница 39: ...7 4 7 3 3 0 7 4 5 g n i r r e t p a d A 1 6 3 3 0 7 4 6 3 3 0 7 4 6 2 3 0 7 4 6 2 3 0 7 4 6 2 3 0 7 4 6 2 3 0 7 4 6 e s a b r e t p a d A 1 4 3 3 0 7 4 4 3 3 0 7 4 5 2 3 0 7 4 5 2 3 0 7 4 5 2 3 0 7 4...

Страница 40: ...accident negligence alteration abuse misapplication or misuse The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual...

Отзывы: