background image

©2019 Pentair plc.   I

  

 15

Troubleshooting - Indicator Lights

There are three LED lights on the Pentair Pentek Solar Drive. The indicator lights and their 
definitions are listed below.

 

AC POWER 

SOLAR  

WARNING 

MODE 

 (Green) 

(Yellow) 

(Red)

 ON 

ON 

ON 

-  Unit is OFF

  FLASHING 

OFF 

OFF 

- Startup

 

ON 

OFF 

OFF 

- Running

 

OFF  

FLASHING 

OFF 

-  Standby

 

OFF 

OFF 

FLASHING 

-   Float Switch

 

OFF 

OFF 

ON 

-  Over Temperature

 

ON 

OFF 

ON 

-  Power Deration

  FLASHING 

OFF 

FLASHING 

- Over-current

 

OFF 

FLASHING 

FLASHING 

-  Short/Open Circuit

 

FLASHING 

FLASHING 

FLASHING 

-  Dry Well Protection

 

OFF Mode

 

Pentair Pentek Solar Drive toggle switch is in the OFF position. 

 

Startup Mode

 

Pentair Pentek Solar Drive is in the process of starting the motor pump.

  

Running Mode

 

Pentair Pentek Solar Drive is running the motor pump.

  

Standby Mode

     There is not enough power from the solar PV panels for  

 

 

Pentair Pentek Solar Drive to start the motor.

 

Float Switch

     Pentair Pentek Solar Drive is turned OFF as a result of input from one  

 

Mode

 

or more external sensors that are connected to the digital input. 

 Over  Temperature

    Pentair Pentek Solar Drive stops operation when the temperature 

 

Mode

 

inside the unit exceeds 80°C/176˚F. 

  Power Deration

     Pentair Pentek Solar Drive still operates but with reduced power 

 

Mode

 

 throughput due to increased operating temperature, or if a load is 
connected with current higher than Over-current Protection  
DIP Switches 4 and 5.

 Over-current

    Pentair Pentek Solar Drive stops operation when it detects high current 

 

Mode

 

 on the motor terminals. This can also be due to a short circuit event if 
the unit is mis-wired. Requires manual restart by cycling power to  
the unit. 

 

Open Circuit

    Pentair Pentek Solar Drive will not start operation if the motor wiring  

 

Mode

 

does not align with DIP switch configuration. 

 

Dry Well 

Pentair Pentek Solar Drive detects dry well condition, and ceases pump 

 

Protection

 

 operation, which is restored after 30 minutes. If dry well indication 
appears faulty, check that 

Over-current Protection

 DIP Switches  

4 and 5 are configured correctly.

Содержание Pentek PSD15

Страница 1: ...pentair com P1061 03 06 19 INSTALLATIONAND OPERATIONMANUAL SOLARDRIVEPSD15 PENTEK...

Страница 2: ...e Installation Requirements 6 Pentair Pentek Solar Drive Hardware 7 Pentair Pentek Solar Drive Overview 8 Pentair Pentek Solar Drive Wiring Instructions 9 Pentair Pentek Solar Drive DIP Switch Setting...

Страница 3: ...tage with a voltage tester NEVER connect power wiring to Drive before mounting the box NEVER handle or service Drive with wet or damp hands Always make sure hands are dry before working on Drive NEVER...

Страница 4: ...ram for a Pentair Pentek Solar Drive operated solar water pumping system is shown in Figure 1 The solar PV array must be connected to an external DC Disconnect and then to the Pentair Pentek Solar Dri...

Страница 5: ...oes not provide branch circuit protection Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes ELECTRICAL MECHANICAL Solar PV open...

Страница 6: ...n a shaded location away from any source of heat and in an area free of vegetation Measures must also be made to protect the unit from damage by unauthorized persons large animals overgrowth flooding...

Страница 7: ...Drive controller should be mounted on a wall or other vertical surface using the back bracket see Figure 5 below On the back side of the unit there are two set screws used to hang the unit on the back...

Страница 8: ...e enclosure is open there are three terminal blocks 1 Solar PV wires 2 Motor pump wires 3 Pump or tank sensor wires More information about sensor wiring and DIP switches is provided on page 8 Figure 6...

Страница 9: ...ugh the right gland float switch signal wires feed through the middle gland and motor load wires feed through the left gland When all conductors are wired into the controller the cover door should be...

Страница 10: ...ed on the motor pump and controller combination being used The default value of RMS current when both switches are OFF is 7A for three phase DIP switches 4 and 5 are to be used to match or exceed the...

Страница 11: ...xample of how tank and well switch signals can be used with a digital input port is shown in Figure 10 For a tank application if the active wire is connected to Position 1 and the return wire usually...

Страница 12: ...sition All LEDs will light up and after a few seconds the Pentair Pentek Solar Drive will try to start the pump indicated by a blinking green light and upon starting the green LED will remain ON 4 If...

Страница 13: ...ugh solar production from the solar panels the yellow LED will start blinking again Shutdown To stop the Pentair Pentek Solar Drive s operation the DC Disconnect should be used Once in the OFF positio...

Страница 14: ...PV Panel Manufacturer Model Number _____________________________________________ No of Solar PV Panels in Series ____________________________________________________ Note to Installer Record the data...

Страница 15: ...e is turned OFF as a result of input from one Mode or more external sensors that are connected to the digital input Over Temperature Pentair Pentek Solar Drive stops operation when the temperature Mod...

Страница 16: ...pping charges associated with this warranty and must request warranty service through the installing dealer as soon as a problem is discovered No request for service will be accepted if received after...

Отзывы: