Pentair MYERS K4563 Скачать руководство пользователя страница 5

K4563  11/08/12

5

contactor in the control panel, breaking the power to 

the pump.

When the motor is stopped due to an overheated 

condition, it will not start until the motor has cooled, 

at which time the control panel will automatically reset 

unless the control panel includes the optional manual-

reset function or is for a hazardous location.

These control panels require that the reset button on 

the control panel be pushed to reset the control panel.

Note:

 

Failure to use proper circuitry and to connect 

the motor overheat protection in the control panel 

would negate all warranties and Factory Mutual 

Approval.

CHECK LIST IF PUMP DOES NOT OPERATE PROPERLY

WARNING: Before handling these pumps and controls, always dis con nect the pow er first. Do not smoke or 
use sparkable electrical devices or flames in a septic (gas eous) or possible septic sump.

Pump does not run in Auto position.

   1.  Check items (1) through (6) per 

condition above.

   2.  Floats may be miswired to 

control panel. Check float type 

(N.O. or N.C.) and hook up by 

re fer ring to the schematic. If the 

start and stop floats are hooked 

in reverse, pump will short

  

  cycle and will not pump the

  

  level  down.

   3.  Is water level in the sys tem high 

enough to ac ti vate the floats?

   4.  If there is enough water in the 

system (with the power turned 

off), mark and disconnect the 

off and on floats. Next, install 

jumper wires in the terminal 

blocks for off and on floats.

  

  Turn power back on, put

  

  H-O-A switch in Auto and see

  

  if pump runs.

   5.  If pump runs with jumper, 

problem is with floats. Remove 

jumpers and troubleshoot floats 

with ohmmeter.

  

6.  If pump does not run in Auto 

mode with jumpers, check Auto 

circuit wiring in panel.

Pump runs, but run light does not energize.

  

1.  Re move light and check with

  

  an  ohmmeter.

   2.  Check run light wir ing.

Pump runs but does not pump down
the wet well.

   1.  On three phase only, pump 

rotation may be wrong. Wiring of 

pump to con trol pan el may be 

re verse  sequenced.

   2.  Impeller may be dragging

  

  in volute due to sol ids.

  

  High amper age draw would 

identify this.

   3.  Refer to the pump manual 

for other possibilities such as 

closed discharge gate valve, etc.

CONDITION

Pump does not run in Hand position.

PROBABLE CAUSE

   1.  Check pump circuit breaker

  

  and control fuse for tripping or 

blown condition.

   2.  Check incoming power voltage 

and control circuit volt age.

   3.  Check overload re lay to see if

  

  it is tripped. Reset relay if 

tripped and check pump current 

with ammeter.

   4. 

With the power off

, check motor 

heat sensor continuity.

   5.  Check wiring of pump to

  

  con trol panel. It should agree 

with  the  sche mat ic.

   6.  Check contactor coil resistance.

Содержание MYERS K4563

Страница 1: ...make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Part K4563 2012 Pent...

Страница 2: ...get metal chips in the components while cutting hole After the hole is cut any metal particles must be removed from the box Failure to do so may result in premature component failure Connect incoming...

Страница 3: ...sure H O A switch is left in the Auto position after start up is completed Pump Start Up Refer to pump Installation and Service Manual PUMP MAINTENANCE WARNING Before handling these pumps and controls...

Страница 4: ...the HIGH WATER and the LAG OVERRIDE float position should be reversed SEAL FAILURE INPUTS Your pump may be equipped with a seal fail moisture sensor Refer to your pump owner s manual to determine if...

Страница 5: ...ugh to ac ti vate the floats 4 If there is enough water in the system with the power turned off mark and disconnect the off and on floats Next install jumper wires in the terminal blocks for off and o...

Страница 6: ...or solids 3 Possible motor failure fault in windings 4 Pump may be miswired to terminal block 5 Voltage and current unbalance Three phase only Voltage unbal ance on three phase power sources can cause...

Страница 7: ...i tor d The meter should in di cate low ohms when it is first connected but as the ca pac i tor becomes charged by the meter it will return to a reading of infinity open circuit 14 Start relay check a...

Страница 8: ...ions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal...

Отзывы: