3

   d. 

Before connecting power to the control panel, 

make sure all con trol switches (e.g. H-O-A switch) 

and protective devices (e.g. breakers) are in the 

Off po si tion. Now connect power to the terminal 

block or the circuit break er as directed by the 

sche mat ic.

   e. 

Control panel must be grounded properly per 

NEC and/or local codes. To facilitate this, a 

ground lug is provided on the control panel.

START-UP OPERATION:

   1.  Check junction box for moisture. Moisture may 

cause chattering of relays/contactors.

   2. 

If pump is single phase with start capacitor, 

start relay and run capacitor in panel. Check 

that pump main and start winding pow er wires 

are con nected to pan el correct ly.  Refer to 

your pump owner’s manual for lead colors.   

   3. 

WARNING: Live voltage can kill! Check 

incoming power volt age to make sure that it is 

correct for panel and pump model.

   4.  Energize control panel. (Turn on power to panel.)

   5.  Check overload relay and verify reset mode

     (if overload is sup plied).

   6. 

WARNING:  Live voltage can kill! Check 

voltage to the panel and at secondary of 

control transformer using a voltmeter. If no 

transformer is supplied, check volt age at

     the circuit breakers. 

   7.  With H-O-A switch in hand, check dis charge to 

ver i fy the pump is run ning. Check for flow. On 

three phase power, check to see if each pump 

has prop er ro ta tion. Wrong ro ta tion will give

  

  low  flow.

   8.  Check full load current with amp probe and 

compare it with the name plate rat ing. On three 

phase pumps, check all three phases. On single 

phase pumps, check black pump lead.

   9.  Check operation of start relay, if supplied on 

single phase panels, per procedure in Item #7 of 

Maintenance Instructions.

10.   With H-O-A switch in Auto, check float operation 

and response to control panel to the float 

operation. For sequence of op er a tion, refer to 

design specification.

 11.   Make sure H-O-A switch is left in the Auto 

position after start-up is completed.

Pump Start-Up:

 Refer to pump Installation and 

Service Manual.

PUMP MAINTENANCE:

WARNING: Before handling these pumps

and controls, always disconnect the power first. 

Do not smoke or use sparkable electrical devices 

or flames in a septic (gaseous) or possible

septic sump.

The maintenance schedule will vary with operating 

and environmental con di tions. It will also vary with the 

specific type of control supplied. The list herein is a 

guide only.

   1.  Exercise breaker through one cy cle. Be careful 

not to overexercise as the break er is not a 

switch ing  device. 

Excessive operations tend to 

affect the trip curve of the breaker. 

   2.  Check contactors and relays for excessive 

humming. This can be accomplished by turning 

pumps on and off in the Hand mode with the 

H-O-A switch.

   3.  Check pump run light(s) by run ning pump(s) in 

Hand mode. Check bulb(s) in any other light(s).

   4. 

With the power off

, check con ti nu ity of all

  

  control  fuses.

   5.  Check voltage at primary and sec ond ary of 

control transformer.

   6.  Check the pump full load amps.

   7.  For 1 phase panels with start circuit, about 5 

seconds after the pump starts check the voltage 

from terminal 1 to terminal 2 on the start relay to 

be sure that the relay has operated.  The voltage 

from terminal 1 to terminal 2 on the start relay 

must exceed 10 VAC.  For some pumps the 

voltage may exceed 400 VAC.  If after 5 seconds 

the voltage from terminal 1 to terminal 2 on the 

start relay does not exceed 10 VAC stop the 

pump as damage to the start capacitor may 

occur in about 15 seconds.  

     If the start relay is not operating check the pump 

and the system voltage to be sure that they 

match. Check the power wiring to ensure that 

the pump is connected properly.  Start the pump 

once more and check that the voltage from the 

terminal for the black wire to the white wire is 

within system tolerance.  Call for help if you 

cannot resolve the problem.

   8.  Check junction boxes for moisture. Moisture may 

cause chattering of relays and contactors. 

Содержание MYERS K4563

Страница 1: ...make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL Part K4563 2012 Pent...

Страница 2: ...get metal chips in the components while cutting hole After the hole is cut any metal particles must be removed from the box Failure to do so may result in premature component failure Connect incoming...

Страница 3: ...sure H O A switch is left in the Auto position after start up is completed Pump Start Up Refer to pump Installation and Service Manual PUMP MAINTENANCE WARNING Before handling these pumps and controls...

Страница 4: ...the HIGH WATER and the LAG OVERRIDE float position should be reversed SEAL FAILURE INPUTS Your pump may be equipped with a seal fail moisture sensor Refer to your pump owner s manual to determine if...

Страница 5: ...ugh to ac ti vate the floats 4 If there is enough water in the system with the power turned off mark and disconnect the off and on floats Next install jumper wires in the terminal blocks for off and o...

Страница 6: ...or solids 3 Possible motor failure fault in windings 4 Pump may be miswired to terminal block 5 Voltage and current unbalance Three phase only Voltage unbal ance on three phase power sources can cause...

Страница 7: ...i tor d The meter should in di cate low ohms when it is first connected but as the ca pac i tor becomes charged by the meter it will return to a reading of infinity open circuit 14 Start relay check a...

Страница 8: ...ions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal...

Отзывы: