background image

MegaTherm Commercial Pool Heating Boiler

Page 9

pool. If this condition exists, follow this procedure to
adjust the switch:

1.

With the boiler on, the filter pump running and
the filter clean, slowly increase the pressure
setting until the boiler shuts off. Slowly decrease
the pressure setting until the boiler comes back
on. Decrease the pressure setting another 2 psi to
complete the switch setting.

2.

Test the setting by closing the manual gas valve
and turning off the filter pump. Turn the
thermostat to the high setting and slowly open
the manual gas valve. The boiler should not try
to fire when the filter pump is off.

If the boiler is installed more than three feet

above the pool level, install an eyeball fitting on the
end of the return line to the pool to create adequate
back pressure that the boiler to operate the pressure
flow safety switch. Never reduce the factory setting of
the pressure switch. For special installation problems,
consult the factory.

SECTION 3.
Operation

3A. Initial Start-Up

3A-1. Initial Filter Cycle on a New Pool

On a newly constructed pool, be sure to run the

filter pump long enough to completely "turn-over" the
pool water before turning on the boiler. This will
insure that any dirt and residue from the construction
will be removed. The filter may clog rapidly during
this period, causing the boiler to severely cycle if it
is on.

3A-2. Starting Instructions

1.

Check the following installation details before
proceeding:

a.

Has the required air supply been provided?

b.

Is the boiler properly vented?

2.

Be sure the filter is clean.

3.

Start the filter pump.

Before placing the boiler in operation, the
automatic safety shutoff devices must be
checked. Once the unit is connected to the gas
piping and after all of the requirements in
Section 2 have been met, follow this procedure:

a.

Before beginning the tests, make sure the
main manual gas valve, and any other firing
valves are in the OFF position.

b.

Make sure the power switch on the boiler is
in the “ON” position. After placing the

manual pilot valves in the open position, and
resetting all safety devices (high limit,
pressure switch, Low-Water-Cutoff, etc.),
pilots can be lit following the procedure
located on the boiler rating plate.

c.

Once the pilots are lit and have been
established for five minutes, the flame
failure response time should be checked as
follows:

System 16:

 (Electronically supervised

standing pilot system standard on propane
gas). Extinguish the pilot flame by placing
the manual pilot valve in the closed
position, and, at the same time, begin
recording the time it takes for the output
signal from the electronic ignition control
to be interrupted. Refer to the electrical
drawing supplied with the boiler for wiring
details. The signal interruption can be
detected either with a test light or a
voltmeter. Because the ignition controls are
in series, the control just upstream of the
gas valves should be tested first. Under no
circumstances should the response time
exceed 5 seconds.

System 18:

 (Intermittent ignition supplied

only for natural gas). With this system,
pilots are automatically lit when the
thermostat calls for heat. The pilots are
permitted a trial period for ignition, then
the system is locked out if it fails to light.
To retry ignition, power to the boiler must
be momentarily interrupted. After the pilot
is initially lit, the trial for ignition time
should be checked by turning off pilot gas,
and, at the same time, monitoring the time
it takes for the audible sparking at the pilot
burner to stop. Under no circumstances
should the trial for ignition exceed 15
seconds because electronic ignition controls
are in series. The control just upstream of
the gas valves should be tested first (refer
to the electrical drawing supplied with the
unit).
Once the trial for ignition period has been
checked, the controls should be reset and
the flame failure response time checked
by following the procedure given for
system 16.

4.

With the pilots lit, initial activation of the main
burners can be achieved by slowly opening the
main manual valve. The result should be a
smooth lighting of the main burners.

Содержание MegaTherm MT 2000

Страница 1: ...sult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL G...

Страница 2: ...it Checkout 10 3B To Start Up System See Section 3A for Initial Start Up 10 3C To Turn Off Boiler 10 3D Spring and Fall Operation 10 3E WinterOperation 10 3E 1 DrainingBoilerBeforeFreezing 10 3E 2 Imp...

Страница 3: ...the Pentair Water Commercial Pool and Spa technical support see page 2 or your local representative with any problems or questions regarding this equipment Experience has shown that most operating pr...

Страница 4: ...unicating directly through the wall to outside air one within 12 inches of the ceiling the other within 12 inches of the floor Each opening should have a minimum free area of one square inch per 4 000...

Страница 5: ...al draft action of the venting system This can create a health hazard by spilling flue products into the boiler room 6 Avoid oversize vent piping or extremely long runs of the pipe which may cause exc...

Страница 6: ...essure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is stamped on the rating plate The regulator is preset at the fact...

Страница 7: ...Piping of System to Boiler 1 Be sure to provide gate valves at the inlet and outlet to the boiler so it can be readily isolated for service 2 The pressure relief valve must be installed in the tapped...

Страница 8: ...ic flow control valve will maintain proper flow through the boiler regardless of the reduced water flow due to a dirty or clogged filter 2J Automatic Chlorinators A concentration of chlorine in the bo...

Страница 9: ...tch on the boiler is in the ON position After placing the manual pilot valves in the open position and resetting all safety devices high limit pressure switch Low Water Cutoff etc pilots can be lit fo...

Страница 10: ...pool water temperature automatically 3C To Turn Off Boiler 1 Turn off main electrical switch 2 Close all manual gas valves 3D Spring and Fall Operation When the pool is not going to be used for a lon...

Страница 11: ...eriodic Service Inspect the heat exchanger tubes of the Model MT pool boiler on a regular basis In most areas and under most operating conditions the MT pool boiler will operate for years without accu...

Страница 12: ...Reassemble in reverse order Be sure to replace the heat exchanger baffles 6 The gas and electric controls installed on the boilers are designed for both dependable operation and long life But the safe...

Страница 13: ...is indicated replace coil or operator Boiler is Pounding Knocking or Emitting Steam from Relief Valves Possible Cause What To Do Lower or no water flow This condition is usually caused by lack of adeq...

Страница 14: ...and remaining screws from flue collector extension 12 12 Install middle rear panel 13 13 Install front panel making sure opening for removable panel is square 19 14 Install front stiffener 184 2450 an...

Страница 15: ...MegaTherm Commercial Pool Heating Boiler Page 15 Figure 12 Outdoor Parts Referenced on page 14...

Страница 16: ...sembly 20011301 20011302 20011303 20011304 20011305 20011306 20011307 12 Rear Closure Assembly 20012401 20012402 20012403 20012404 20012405 20012406 20012407 13 Heat Shield Support Bracket 20003201 20...

Страница 17: ...MegaTherm Commercial Pool Heating Boiler Page 17 Figure 13 Parts Identification Indoor parts only For tiles see Figure 15...

Страница 18: ...20012303 20012304 20012305 20012306 20012307 indoor only 35 Flue End Assembly 20012000 20012000 20012000 20012000 20012000 20012000 20012000 2 2 2 2 2 2 2 36 Upper End Assembly 20011900 20011900 2001...

Страница 19: ...shown 2 2 2 2 2 49 b Pilot Relay Standing Pilot W003000 W003000 W003000 W003000 W003000 W003000 W003000 not shown 2 2 2 2 2 50 Pilot Burner Johnson W0034700 W0034700 W0034700 W0034700 W0034700 W00347...

Страница 20: ...1 805 553 5000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this...

Отзывы: