7
10-1008-62 rev 10
Inlet Air Filter Con’t
It is recommended that power to the air conditioner be interrupted intentionally when abnormally high
compressor operating temperature causes automatic shutdown of the unit. The above described
shutdown is symptomatic of clogged or dirty filter, thus causing a reduction in cooling airflow across the
surface of the compressor and condenser coil.
Do not run the air conditioner for extended periods of time with the filter removed. Particles of dust, lint,
etc., can plug the fins of the condenser coil, which will give the same reaction as a plugged filter. The
condenser coil is not visible through the filter opening, so protect it with a filter.
Continued operation under the above conditions can and will damage and shorten compressor life. The
air conditioner features an easily removable inlet filter to facilitate necessary cleaning. There should be no
reason to neglect this necessary maintenance.
How To Remove, Clean or Install a New Inlet Air Filter
RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust
holding capacity and a minimum amount of resistance to air flow. Because they are constructed entirely
of aluminum they are lightweight and easy to service. Optimum filter performance is maintained by
recoating the filters after washing with RP Super Filter Coat adhesive. To achieve maximum performance
from your air handling equipment, air filters should be cleaned on a regular basis.
The inlet air filter is located behind the front grille. To remove the grille, remove (2) screws and pull top
edge of grille forward. The filter may now be removed and cleaned or new filter installed. Reinstall grille.
Cleaning Instructions:
1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
2. After flushing allow filter to drain. Placing it with a corner down will assure complete drainage.
3. Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides for
maximum concentration of adhesive.
Condenser and Evaporator Air Movers
Blower and impeller motors require no maintenance. All bearings, shafts, etc. are lubricated during
manufacturing for the life of the motor.
If the condenser blower motor (ambient blower) should fail, it is not necessary to remove the air
conditioner from the cabinet or enclosure to replace the blower. The condenser blower is mounted on its
own bulkhead and is easily accessible by removing the front cover.
Caution: Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly
deteriorate filters, condenser coils, blowers and motors, etc. Contact McLean Thermal for special
recommendations.
Refrigerant Loss
Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks.
Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection
equipment during manufacture may require repair or recharging of the system. This work should only be
performed by qualified professionals, generally available through a local, reputable air conditioning repair
or service company.
Refer to the data on the nameplate, which specifies the type of refrigerant and the charge size in ounces.