The Password screen displays a numeric keypad.
Figure 17 Password Screen
• Enter the master settings password
1201
and press
to
continue to the main Master Settings screen, or press
to return to the Home screen.
After entering the correct password and pressing , the main
Master Settings screen is displayed.
Figure 18 Main Master Settings Screen
While in the Master Settings screens, press to save all
set parameters to a custom profile (see "NON-FACTORY
SETTINGS" on page 15) or press the
Home
button to
return to the Home screen.
Features of the Master Settings screens are described
below. See MASTER SETTINGS PROGRAMMING and MASTER
SETTINGS REFERENCE CHART for more detailed information.
• format
: Contains settings for Language, Units, Hardness
Units, Assistance Name, Assistance Phone, and
Assistance Interval. See TOUCHSCREEN CONTROL QUICK
START for more information about these settings.
• valve
: Contains settings for System, Valve, and
Regeneration Type.
• regen
: Contains settings for Regen Flow.
• relay
: Contains settings for Aux 1 and Aux 2 relays.
• meter
: (time clock systems) Contains settings for Meter
Types, emergency regeneration
• settings review
: Displays a summary of all programmed
settings.
Press the screen navigation arrow at the top right of the screen
to navigate to the secondary Master Settings screen.
Figure 19 Secondary Master Settings Screen
• water saver regen:
Contains settings for setting
regenerations to save water by reducing backwash and
rinse time on a particular interval
• remote regen:
Contains settings for triggering a
regeneration via a remote input
• cl generation/low salt:
(international version only)
Contains settings to trigger chlorine generator for the
control
Water Saver Regeneration
From the secondary Master Settings screen (Figure 19) press
the
water saver regen.
button to display the Water Saver
Regen screen (Figure 20).
Figure 20 Water Saver Regen Screen
• water saver regen:
reduces backwash and rapid rinse
times on a particular interval. The reduced backwash
time is 50% less than the backwash time (rounded down
to the nearest minute, e.g. if the backwash time is set to
10 minutes, enabling the water saver regen function will
reduce the backwash time to 5 minutes).The reduced
rapid rinse time is 66% less than the rapid rinse time
(rounded down to the nearest minute, e.g. if the rapid
rinse time is set to 10 minutes, enabling the water
saver regen function will reduce the backwash time to 3
minutes).
• range:
1-25 regenerations (for example, a setting of 3
will produce 1 normal regeneration then 3 reduced water
saving regenerations).
TOUCHSCREEN CONTROL FEATURES
continued
FLECK
5810 & 5812 XTR2 Service Manual • 11