Procedure:
Open the control head (follow the instruc ons in chapter 8 “Opening and closing the housing” if in doubt)
Prepare the cable by stripping back the outer sheath to expose approximately 120mm of the cores. Strip each core to
expose 6 to 8mm of bare copper.
Insert the cable through the cable gland un l the outer sheath is able to be secured by ghtening the gland
Twist each core
fi
rmly before
fi
ng to the terminals of the 6
‐
way terminal block as in Fig 12.
Use a screwdriver or similar tool to depress the spring terminal latches, insert the wire and release the latch.
Close the housing (follow the instruc ons in chapter 8 “Opening and closing the housing” if in doubt)
NOTE!
Ensure IP protec on is maintained!
To ensure the control head IP ra ng is maintained the cable gland nut must be ghtened securely, the cap O
‐
ring must
be in good condi on and in place and the relief valve must be
fi
ed correctly and it’s O
‐
ring in place.
All unused air connec ons should be
fi
ed with a sealing plug
Fig 12: Electrical connec on
For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer
fi
ed product
Содержание F783E
Страница 1: ...F783E Ex ia Pg 1 00 ISN 203_Rev B 29 01 2021 Opera ng Manual ...
Страница 5: ...F783E Ex ia Pg 5 00 ISN 203_Rev B 29 01 2021 This page le blank ...
Страница 13: ...F783E Ex ia Pg 13 00 ISN 203_Rev B 29 01 2021 This page le blank ...
Страница 15: ...F783E Ex ia Pg 15 00 ISN 203_Rev B 29 01 2021 Fig 1 Structure of the control top ...
Страница 21: ...F783E Ex ia Pg 21 00 ISN 203_Rev B 29 01 2021 Fig 6 Sec on view of control head on linear actuator ...