background image

 2.13" 

 0.18" 

#10

 

 

 

 

Flat

NOTE:

1. Tighten screws of all unused galleries to the specified torque above.

2. For multiple phase assemblies, join blocks together before installing on DIN Profile.

3. When protected by 200 ampere Class J or T fuse, this terminal block is rated for use 

on a circuit capable of delivering no more than 100kArms symmetrical amperes, 600 volts maximum.

4. The conduit ends shall be provided with a plastic conduit bushing.

cURus is a registered Recognized Component Mark of Underwriters Laboratories, Inc

UL is a registered trademark of Underwriters Laboratories, Inc.

CSA mark is a registered trademark of CSA Group Certification & Testing Inc.,

I = 85A

Ui = 600V AC/DC

*For Short Circuit Current Rating up to 100kA see UL file E198301

TECHNICAL SUPPORT

www.erico.pentair.com

IP7802_L

2 OF 2

INSTRUCTION SHEET

Pentair, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by Pentair or its global affiliates. All other 

trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

WARNING:

Pentair products shall be installed and used only as indicated in Pentair product instruction sheets and training materials. Instruction sheets are available at 

1.

www.erico.pentair.com

 and from your Pentair customer service representative.  

Pentair products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be 

completely

 followed to ensure proper and safe installation and performance.  

3.

Improper installation, misuse, misapplication or other failure to completely follow Pentair's instructions and warnings may cause product malfunction, property 

4.

damage, serious bodily injury and/or death, and void your warranty.

SAFETY INSTRUCTIONS: 

All governing codes and regulations and those required by the job site must be observed. 

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

UD80A

569010

© 2004-2016 Pentair All Rights 

Reserved