Capacity Setting

Move the jumper to the set of pins next to the word CAPACITY 

(Figure 9). Press the black TIME SET button until the correct 

capacity value is displayed. The capacity range is 1 to 99 

kilograins. Refer to the Suggested Salt Dial Settings table (1).
Return the jumper to the top set of pins next to the word TIME 

and replace the access door. The jumper must NOT be left 

on any pins other than the top pair next to the word TIME. 

Otherwise, the unit may show a blank display.

NotE:   

A spare jumper is located on the bottom set of pins.

In the event that the hardness or capacity setting must be 

changed, simply follow the appropriate steps described above.

Calendar override Setting

1.  Disconnect power.
2.  Place jumper on Pin A and reconnect power.
3.  Move jumper to Pin B. A zero will appear, indicating 

zero days of calendar override. All 460i controllers are 

preprogrammed in this manner at the manufacturer.

4.  Depress the black TIME SET button. The numbers will roll 

from “0” to “15.” Release the switch at the desired number 

of days for the calendar override. For example, releasing 

the switch at “10” would program a 10-day  

calendar override.

5.  Disconnect power.
6.  Place jumper back on TIME and reconnect power.
7.  The calendar override program is maintained during power 

outages by the NOVRAM circuitry.

8.  To remove the calendar override, follow the same steps 

above and program back to “0.”

460tC Control

460TC

DAYS

CLOCK

PM Indicator

Hour Time Display

Access 

Door

Indicator Knob

Timer Locking Pin

Raised Tab

Jumper

Spare 

Jumper

Transformer 

Plug Receptacle

Time Set Button

Figure 10  

Programming

Plug the wall-mount transformer into a functioning electrical 

outlet that is not controlled by a switch. Plug the transformer 

into the transformer plug receptacle on the control.
Open the access door by pushing the raised tab on the door 

toward the left while pulling the tab out (Figure 10).

time of Day Setting

With the jumper on the set of pins next to the word TIME 

(Figure 11), set the time of day to the closest hour by pressing 

the black TIME SET button. PM hours are indicated by a light 

next to the letters PM on the display window.

NotE:   

the use of a small needle-nose pliers will aid in 

moving the jumper.

NotE:   

the unit is factory set to regenerate at 2:00 a.m. If 

you prefer to have the unit regenerate at an earlier 

or later time, simply set the current time of day 

accordingly (e.g., to have the unit regenerate at 4:00 

a.m.—two hours later—set the clock two hours 

earlier than the actual time of day).

NotE:   

the timer locking Pin should always be horizontal 

(Figure 10) during operation.

Days Setting

Move the jumper to the set of pins next to the word DAYS 

(Figure 12). Press the black TIME SET button until the desired 

number of days between regeneration is displayed. The range 

is from 1 to 30 days.

TIME

DAYS

CLOCK

TIME

DAYS

CLOCK

TIME

DAYS

CLOCK

Figure 11   

Figure 12   

Figure 13   

Clock Setting

Move the jumper to the set of pins next to the word CLOCK 

(Figure 13). Press the black TIME SET button until the desired 

clock setting is displayed. The clock range is 0 or 1. Select 0 

for the standard AM/PM clock or select 1 for a 24 hour clock.
Return the jumper to the top set of pins next to the word TIME 

and replace the access door. The jumper must NOT be left 

on any pins other than the top pair next to the word TIME. 

Otherwise, the unit may show a blank display.

NotE:   

A spare jumper is located on the bottom set of pins.

400 SErIES CoNtrol SEttINgS 

continued

Содержание AUTOTROL 460i

Страница 1: ... Performa Valve with 400 Series Control Water Conditioning Control System Service Manual 460TC DAYS CLOCK 460TC BRINE SLOW RINSE BACKWASH FAST RINSE REFILL CONDITIONED WATER MANUAL REGENERATION PRESS BUTTON RELEASE PRESS TO SETTIME ...

Страница 2: ...sible 4 Do not install any unit closer to a water heater than a total run of 10 feet 3 m of piping between the outlet of the conditioner and the inlet to the heater Water heaters can sometimes overheat to the extent they will transmit heat back down the cold pipe into the unit control valve Hot water can severely damage the conditioner A 10 foot 3 m total pipe run including bends elbows etc is a r...

Страница 3: ...ional 2 feet 61 cm for each additional 10 psi 0 69 bar 4 Where the drain line is elevated but empties into a drain below the level of the control valve form a 7 inch 18 cm loop at the far end of the line so that the bottom of the loop is level with the drain line connection This will provide an adequate siphon trap 5 Where the drain empties into an overhead sewer line a sink type trap must be used...

Страница 4: ...k initial fill With a bucket or hose add approximately 4 gallons 15 liters of water to brine tank If the tank has a salt platform above the bottom of the tank add water until the level is approximately 1 inch 25 mm above the platform 5 Place the conditioner into operation A With the water supply valve completely open carefully advance the indicator knob COUNTERCLOCKWISE to the center of the BRINE ...

Страница 5: ... Time Set Button Figure 6 Programming Plug the wall mount transformer into a functioning electrical outlet that is not controlled by a switch Plug the transformer into the transformer plug receptacle on the control Open the access door by pushing the raised tab on the door toward the left while pulling the tab out Figure 6 Time of Day Setting With the jumper on the set of pins next to the word TIM...

Страница 6: ...ogramming Plug the wall mount transformer into a functioning electrical outlet that is not controlled by a switch Plug the transformer into the transformer plug receptacle on the control Open the access door by pushing the raised tab on the door toward the left while pulling the tab out Figure 10 Time of Day Setting With the jumper on the set of pins next to the word TIME Figure 11 set the time of...

Страница 7: ...lt used during the regeneration cycle Water will dissolve and absorb salt only until it becomes saturated A given amount of brine salt saturated water contains a specific amount of salt The salt dial controls the amount of brine used during the regeneration cycle e g when set at 15 pounds 6 8 kg the amount of brine the conditioner will use for each regeneration will contain 15 pounds 6 8 kg of sal...

Страница 8: ...talling the camshaft the control should be in SERVICE position When the camshaft is positioned cams will make contact with valves to force them open PREVENTIVE MAINTENANCE Injector Screen and Injector Inspect and clean brine tank and screen filter on end of brine pickup tube once a year or when sediment appears in the bottom of the brine tank Clean injector screen and injector once a year 1 Unplug...

Страница 9: ...truction of the modern water conditioner will not support bacterial growth nor will these materials contaminate a water supply However the normal conditions existing during shipping storage and installation indicate the advisability of disinfecting a conditioner after installation before the conditioner is used to treat potable water In addition during normal use a conditioner may become fouled wi...

Страница 10: ... stainless steel pipe adapters 3 4 inch 1 inch 25 mm CPVC tube adapters Brine Line Connection 3 8 inch NPT male Drain Line Connection 3 4 inch NPT male Optional Bypass Valve Rotating handles full 1 inch porting reinforced plastic Control Module Tank Adapter Reinforced plastic Rubber Goods Compounded for cold water service Brine Refill Control 1 to 10 lbs 0 45 to 4 5 kg of salt or 3 to 19 lbs 1 4 t...

Страница 11: ...otal PSI bar M hr 3 GPM Injector 1031365 C in a 268 Valve 20 40 60 80 100 120 400 600 800 1000 1200 1400 1600 1800 Brine Draw Rinse Total PSI bar M hr 3 GPM Injector 1031364 B in a 268 Valve 0 30 0 25 0 20 0 15 0 10 0 05 0 00 1 25 1 00 0 75 0 50 0 25 0 00 20 40 60 80 100 120 400 600 800 1000 1200 1400 1600 1800 PSI bar M hr 3 GPM Injector 1030272 D in a 268 Valve 0 30 0 25 0 20 0 15 0 10 0 05 0 00...

Страница 12: ...es Control Water Conditioning Control System CONTROL VALVE Identification of Control Valving 1 Brine Valve 2 Bypass Valve 3 Inlet Valve 4 Outlet Valve 5 Refill Valve 6 Rinse Drain Valve 7 Backwash Drain Valve Valve Disc Principle of Operation ...

Страница 13: ...n 4 Closed 5 Closed 6 Open 7 Closed 5 Brine Refill Position Brine Adjustment Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 5 4 1 3 2 6 7 Valve No 1 Closed 2 Closed 3 Open 4 Open 5 Open 6 Closed 7 Closed FLOW DIAGRAMS 1 Service Position Brine Adjustment Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 5 4 1 3 2 6 7 Valve No 1 Closed 2 Closed 3 Open 4 Open 5 Closed...

Страница 14: ...226 Screen Cap Assembly 11 1 1010429 O Ring 12 1 1035622 Tank Ring 13 1 Plumbing Adapter Kits 1001606 3 4 inch Copper Tube Adapter Kit 1001670 1 inch Copper Tube Adapter Kit 1041210 1 1 4 inch Copper Tube Adapter Kit 1001608 22 mm Copper Tube Adapter Kit 1001609 28 mm Copper Tube Adapter Kit 1001613 3 4 inch CPVC Tube Adapter Kit 1001614 1 inch CPVC Tube Adapter Kit 1001615 25 mm CPVC Tube Adapter...

Страница 15: ...Item No QTY Part No Description 1 1 440i Control 6 day or 7 day 2 1 460i Control 3 1 4001086 460TC Control 4 1 1040930 1265 Bypass Not Shown 1 1000811 Transformer 440i 460i 1 1000907 Transformer Extension Cord 15 feet 4 6 m 1 1034264 Y Splitter run 2 units from 1 transformer 1 1007776 Jumper 460TC Control 3 460TC DAYS CLOCK 1265 Bypass 4 BYPASS BYPASS ...

Страница 16: ... Valve 3 or 4 not closed during brine draw causing refill Flush out foreign matter by holding disc open and manually operating valve stem Air leak in brine line Check all connections in brine line for leaks Refer to instructions System using more or less salt than salt control is set for Inaccurate setting Correct setting Foreign matter in controller causing incorrect flow rates Remove variable sa...

Страница 17: ...r than time of day Electrical interference Disconnect power to unit Restore power and reset time of day Defective circuit board Replace timer No water flow display when water is flowing 460TC has no meter Bypass valve in bypass Shift bypass valve to not in bypass position Meter probe disconnected or not fully connected to meter housing Fully insert probe into meter housing 460TC has no meter Restr...

Страница 18: ...d Replace timer Incorrect hardness and capacity settings Set to correct values See Programming section Run out of soft water between regenerations Improper regeneration Repeat regeneration making certain that correct salt dosage is used Fouled softener resin Use resin cleaner Use of resin cleaners in an unvented enclosure is not recommended Incorrect salt setting Set salt control to proper level S...

Страница 19: ...Autotrol Performa Valve with 400 Series Control Water Conditioning Control System 19 ...

Страница 20: ...ks and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal opportunity employer 1222945 REV M FE14 2013 Pentair Residential Filtration LLC All Rights Reserved For Autotrol Product Warranties visit Autotrol para las garantías de los productos vis...

Отзывы: