11
E-03-601 (02-15-22)
PUMP TROUBLESHOOTING
Below is a list of common problems and the probable causes.
PUMP WILL NOT START
1. No power to the motor. Check for blown fuse or open circuit
breaker.
2. Selector switch may be in the Off position.
3. Control circuit transformer fuse may be blown.
4. Overload heater on starter may be tripped. Push to reset.
PUMP WILL NOT START AND OVERLOAD HEATERS TRIP
1. Turn off power and check motor leads with Megger or
ohmmeter for possible ground.
2. Check resistance of motor windings. All 3 phases should
exhibit the same reading.
3. If no grounds exist and the motor windings check OK,
remove pump from sump and check for clogged or blocked
impeller.
PUMP OPERATES WITH SELECTOR SWITCH IN HAND POSITION
BUT WILL NOT OPERATE IN AUTO POSITION
1. This indicates trouble in the float level control or the
alternator relay.
2. Check control panel for trouble.
PUMP RUNS BUT WILL NOT SHUT OFF
1. Pump may be air locked. Turn pump off and let set for
several minutes, then restart.
2. Lower float control may be hung-up in the closed position.
Check in sump to be sure control is free.
3. Selector switch may be in the Hand position.
TROUBLESHOOTING
PUMP DOES NOT DELIVER PROPER CAPACITY
1. Discharge gate valve may be partially closed or partially
clogged.
2. Check valve may be partially clogged. Raise level up and
down to clear.
3. Pump may be running in wrong direction. Low speed pumps
can operate in reverse direction without much noise or
vibration.
4. Discharge head may be too high. Check total head with
gauge when pump is operating. Total head is discharge
gauge pressure converted to feet plus vertical height from
water level in sump to center line of pressure gauge in
discharge line. Gauge should be installed on pump side of
all valves. Multiply gauge pressure in pounds by 2.31 to get
head in feet.
5. If pump has been in service for some time and capacity falls
off, remove pump and check for wear or clogged impeller.
MOTOR STOPS AND THEN RESTARTS AFTER SHORT PERIOD
BUT OVERLOAD HEATERS IN STARTER DO NOT TRIP
1. This indicates heat sensors in the motor are tripping due
to excessive heat. Impeller may be partially clogged giving
a sustained overload but not high enough to trip overload
heater switch.
2. Motor may be operating out of liquid due to a failed level
control.
3. Pump may be operating on a short cycle due to sump being
too small or from water returning to sump due to a leaking
check valve.
IF YOU HAVE ANY QUESTIONS REGARDING THE INSTALLATION, OPERATION, MAINTENANCE OR
TROUBLESHOOTING OF THE PUMP, PLEASE CALL PENTAIR AT 855-274-8947.
Содержание HPS4HDX
Страница 3: ...3 E 03 601 02 15 22 PAGE INTENTIONALLY LEFT BLANK ...
Страница 17: ...17 E 03 601 02 15 22 WIRINGDIAGRAMS ...
Страница 18: ...18 E 03 601 02 15 22 WIRINGDIAGRAMS ...