6

  

E-03-558 (07-05-20)

PUMP OPERATIONS STARTING SYSTEM

1.  Double check all wire connections.

2.  Turn pumps to Off position on H-O-A switches.

3.  Turn on breakers.

4.  When using single phase pumps, make sure red pump lead 

is connected to capacitor circuit. Connect amprobe to pump 
power cord and turn pump on. The pump will show high amp 
draw momentarily, then as pump comes off start wirings, amps 
will drop to  normal nameplate amps. 

5.  When using three phase pumps (230/460/575), turn the 

H-O-A switch to Hand position on one pump and notice 
operation. If pump is noisy and vibrates, rotation is wrong. 
To change rotation, interchange any two line leads to pump. 
Do not interchange main incoming lines. Check rotation of 
all pumps in this same manner. 

6.  Now set both H-O-A switches to Auto position and allow 

water to rise in sump until one pump starts. Allow pump to 
operate until the level drops to turn-off point.

7.  Allow sump level to rise to start other pump(s). Notice run 

lights in panel. Pumps should alternate on each successive 
cycle of operation. 

8.  Turn both H-O-A switches to Off position and allow sump to 

fill to the override control level(s).

9.  Turn switches to Auto position, and pumps should start and 

operate together until level drops to turn-off point.

10.  Repeat this operation and cycle several times before 

leaving the job.

11.  Check voltage when pumps are operating and check the 

amp draw of each pump. Check amps on each wire as 
sometimes a high leg will exist. For excessive voltage on 
one leg, the electric utility company should be consulted.

PUMP MAINTENANCE 

As the motors are oil filled, no lubrication or other maintenance is 
required.

If the heat sensor and seal failure are hooked up properly, no 
attention is necessary as long as the seal failure indicator light 
does not come on. To ensure continuity of the seal sensor leads, 
a test light is provided on intrinsically safe Hydromatic panels as 
standard equipment.

Pump should be checked every quarter for corrosion and wear.

 Before handling these pumps and controls,always 

disconnect the power first. Do not smoke, use flames or devices 
that can produce electrical discharge or sparks in a septic 
(gaseous) or possible septic sump.

FIELD SERVICE ON HYDROMATIC ORDINARY LOCATION PUMPS

Ordinary location submersible motors that are out of warranty 
can be serviced in the field by any reliable motor service shop.

Any pump that is in warranty must be returned to the factory for 
service or repaired at an authorized Pentair Hydromatic service 
center. Charges will not be allowed if (in warranty) pump is not 
taken to an authorized Pentair Hydromatic service center. When 
field service is performed on a pump, these instructions should be 
carefully followed.

FIELD SERVICE ON HYDROMATIC HAZARDOUS LOCATION PUMPS

Hydromatic hazardous location pumps must be returned to the 
factory for electrical and motor service. Any repair not at an 
authorized service center will void the Factory Mutual (FM) listing. 
This will ensure the integrity of the hazardous location rating of 
the pump and comply with our warranty requirements. 

The quick disconnect cords, upper and lower seal, volute 
and impeller components may be repaired or replaced by an 
authorized Hydromatic service facility without compromising the 
hazardous location rating to the pump.

Any time a seal is disturbed, it must be replaced.

Check the pump for proper rotation before returning to service.

ADJUST CUTTER CLEARANCE ON CHOPPER PUMP

 Disconnect power before adjusting chopper 

clearance; always keep fingers and hands away from chopper 
parts.

1.  First install the chopper plate (Item D) into the volute. It may 

be helpful to install ½-20 studs into the chopper plate to line 
up the holes with the corresponding volute holes. You may 
have to tap the plate all the way down with a rubber hammer.

2.  Remove the studs and replace with four ½-20 x 1 (Item A) in 

long socket head screws from beneath the volute, do not 
tighten.

3.  Install motor with impeller mounted,  tighten motor housing 

bolts to the volute

4.  Install the chopper retainer ring (Item B) and tighten the four 

3/8 -16 x 1" long (Item C) socket head cap screws to force the 
chopper plate up against the impeller and chopper blade

5.  Next  back off  these 3/8-16 (Item C) bolts one quarter of a 

turn. This should give you .015 clearances.

6.  Tighten the outer four ½ -20 screws (Item A) to 75-85 Ft-lbs.

7.  Measure the clearance with a feeler gage it should be 

between .010 and .015.

8.  Spin impeller with a hex wrench on the Impeller hub screw or 

use a wooden pry bar to spin impeller to make sure there is no 
rub.

9.  If you hear or feel a rub readjust the clearance by loosening 

the inner 3/8-16" screws evenly and tightening the ½- 20 
screws.

PUMP OPERATIONS & MAINTENANCE

Содержание C4H(X)P

Страница 1: ...t 056255581 2020 All Rights Reserved INSTALLATIONAND OPERATIONMANUAL SUBMERSIBLE SOLIDSHANDLING PUMP C4H X P H4Q X P S4K X P S4L X P S4LV X P S4B X P S6L X P S6A X P S8F X P Used in hazardous locations Class I Division I Groups C D FM ...

Страница 2: ...TABLEOFCONTENTS SECTION PAGE Safety Information 3 General Information 4 Pump Installation 5 Pump Operation Maintenance 6 Troubleshooting 7 Parts List 8 Wiring Diagrams 15 Warranty 16 ...

Страница 3: ...ial An improperly sized tank can cause the pump to cycle and lead to pump damage This may require a larger pressure tank than is normally used CALIFORNIA PROPOSITION 65 WARNING This product and related accessories contain chemicals known to the State of California to cause cancer birth defects or other reproductive harm ELECTRICAL SAFETY ELECTROCUTION HAZARD Must be installed by a qualified profes...

Страница 4: ...inding temperature the starter in the panel breaks power to the pump Once the sensor resets the starter is automatically reset for FM for continued operation of the pump This circuitry is supplied in a Hydromatic control panel The sensors are set to trip at 130 C Failure to install such circuitry would negate FM approvals and all warranties by Hydromatic POWER CORDS The power cord and heat sensor ...

Страница 5: ...nge Pumps shipped from the factory as 460 volt 3 phase cannot be rewired to any other voltage TO RE WIRE THE PUMP FROM 230V TO 460V 3 PHASE Only a 230V pump from the factory is considered dual voltage a cord label clearly states the factory wound voltage 1 Remove all six 7 cap screws then raise the cord cap assembly enough to slip a prying instrument on opposite sides between the cord cap casting ...

Страница 6: ...ble motors that are out of warranty can be serviced in the field by any reliable motor service shop Any pump that is in warranty must be returned to the factory for service or repaired at an authorized Pentair Hydromatic service center Charges will not be allowed if in warranty pump is not taken to an authorized Pentair Hydromatic service center When field service is performed on a pump these inst...

Страница 7: ...city 1 Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can operate in reverse direction without much noise or vibration 4 Discharge head may be too high Check total head with gauge when pump is operating Total head is discharge gauge pressure converted ...

Страница 8: ...5 CORD CAP ASSEMBLY 4 4 W 1 25 107550312 SEAL PLATE 1 132531001 OIL DIELECTRIC VARIES PUMP PARTS LIST 1 2 3 4 5 7 8 12 11 15 16 18 19 10 A1 A2 A4 24 6 16 16 17 13 14 20 21 A3 22 23 9 20 25 250 FRAME PUMPS Ref Part No Part Description Qty 1 28012D000 MOTOR HOUSING 1 2 27966D010 BEARING HOUSING 1 3 27882A009 TERMINAL BLOCK 1 4 06106A069 SCREW CAP SKT HD 2 5 110650043 SCREEN 1 6 19331A009 WASHER SPRI...

Страница 9: ...1 005700181 005700181 005680191 D7 SCREW MACHINE NOT SHOWN SEE VOLUTE ASSY 008290061 3 008290061 3 N A SEE VOLUTE ASSY SEE VOLUTE ASSY 008290091 4 SEE VOLUTE ASSY N A D8 WEAR RING SEE VOLUTE ASSY 136900003 136900003 N A SEE VOLUTE ASSY SEE VOLUTE ASSY 136900003 SEE VOLUTE ASSY N A D9 CUTTER PLATE N A N A N A N A N A N A N A N A 153600002 D10 CUTTER INSERT N A N A N A N A N A N A N A N A 153320014 ...

Страница 10: ...A027 A4 SPACER 076650041 076650041 076650041 076650121 076650121 076650121 CONNECTOR 12672A001 12672A001 ITEM 8 POLE 870 RPM 10 15 HP 10 15 HP 10 15 HP 208 230 3 60 460 3 60 575 3 60 A1 STATOR 27963D003 27963D003 27963D603 A2 ROTOR SHAFT ASSEMBLY 27963D011 27963D011 27963D011 A3 BOLT STATOR 4 005560081 005560081 005560081 A4 SPACER 076651001 076651001 076651001 CONNECTOR 12672A001 ITEM 6 POLE 1150...

Страница 11: ...8 110430382 S4LV X P4000FC 40 460 3 6 4 11 5 110430012 S4LV X P4000GC 40 575 3 8 4 11 5 110430012 1150 RPM S4LV X P750DB 7 5 208 3 8 4 10 110430042 S4LV X P750EB 7 5 230 3 8 4 10 110430042 S4LV X P750FB 7 5 460 3 10 4 10 110430042 S4LV X P750GB 7 5 575 3 10 4 10 110430042 S4LV X P1000DB 10 208 3 8 4 11 25 110430082 S4LV X P1000EB 10 230 3 8 4 11 25 110430082 S4LV X P1000FB 10 460 3 10 4 11 25 1104...

Страница 12: ...025940002 S4L X P750FA 7 5 460 3 10 4 11 88 025940002 S4L X P750GA 7 5 575 3 10 4 11 88 025940002 S6L X P Cat No HP Volt Ph Cord Trim Impeller 1750 RPM S6L X P2000DC 20 208 3 6 4 9 88 025940372 S6L X P2000EC 20 230 3 6 4 9 88 025940372 S6L X P2000FC 20 460 3 8 4 9 88 025940372 S6L X P2000GC 20 575 3 8 4 9 88 025940372 S6L X P2500DC 25 208 3 4 4 10 25 025940072 S6L X P2500EC 25 230 3 6 4 10 25 0259...

Страница 13: ... P2500FC 25 460 3 8 4 10 13 025940172 S8F X P2500GC 25 575 3 8 4 10 13 025940172 S8F X P3000EC 30 230 3 4 4 10 5 025940082 S8F X P3000FC 30 460 3 8 4 10 5 025940082 S8F X P3000GC 30 575 3 8 4 10 5 025940082 S8F X P4000FC 40 460 3 6 4 11 38 025940202 S8F X P4000GC 40 575 3 8 4 11 38 025940202 1150 RPM S8F X P750DB 7 5 208 3 8 4 10 38 025940162 S8F X P750EB 7 5 230 3 8 4 10 38 025940162 S8F X P750FB...

Страница 14: ...20 460 3 8 4 12 136920012 S4B X P2000GB 20 575 3 10 4 12 136920012 870 RPM S4B X P1000DA 10 208 3 8 4 12 136920012 S4B X P1000EA 10 230 3 8 4 12 136920012 S4B X P1000FA 10 460 3 10 4 12 136920012 S4B X P1000GA 10 575 3 10 4 12 136920012 S4LV X P CAT NO HP VOLT PH CORD TRIM IMPELLER 1750 RPM S4LV X P5000FC 50 460 3 4 4 12 110430002 S4LV X P5000GC 50 575 3 6 4 12 110430002 S6A X P CAT NO HP VOLT PH ...

Страница 15: ...15 E 03 558 07 05 20 WIRINGDIAGRAMS ...

Страница 16: ...ll dual seal pumps Under no circumstance will Pentair Hydromatic be responsible for the cost of field labor travel expenses rented equipment removal reinstallation costs or freight expenses to and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or main tain the...

Отзывы: