background image

10 

10

1.

 

Connect the ends of the connecting hoses (hot and cold water supply) to the respective 
ports on the tub. Ensure that there are sealing gaskets within the swivel fittings on the 
hoses. 

2.

 

Connect the drain (waste) of the tub to the facility’s drain system. 

3.

 

The system needs to be checked for any leaks in the entire system. However, the 
electrical connections must be made prior to doing this. Once the electrical connections 
have been made, continue with step 4. 

4.

 

Open the facility’s supply valves to the tub and check for leaks. If no leaks are found, 
check the entire plumbing system for any leaks. Look for leaks while each of the 
following systems are running: “Tub fill”, “Shower”, and “Disinfecting”. 

 

Electrical Connections: 

 

  

Warning: 

This unit is to be connected only by a licensed electrician.  A minimum of 15 amp 120 volt 
service is required with ground fault circuit interrupter. 
 

1.

 

Remove the covers from the electrical box of the tub (and reservoir). 

2.

 

For tubs with reservoirs, connect the reservoir electrical supply lead to the tub’s electrical 

kit.  

a.

 

Remove the hole-plug from the left side of the tub electrical box. 

b.

 

Run the cable lead through that hole and secure using the cord restraint 
and nut provided. 

c.

 

Connect the line wire to the line distribution bar located in the upper 
right corner of the tub’s electrical box. It will have only black wires 
connected to it.  See figure 10. 

d.

 

Then connect the neutral and ground wires, neutral, and ground 
terminals respectively. 
These are labeled 
accordingly. 

e.

 

Replace the cover of the 
reservoir’s electrical box. 

3.

 

Run flexible conduit and the proper size 

wires, from the facility’s junction box to the 
connecting point of the tub’s electrical 
enclosure. (Located inside the large access door 
opening on the “left” side of the tub.) 

4.

 

Connect the ground to the “protective earth” 

(ground) bar.  

5.

 

Connect the neutral wire to neutral bar 

marked “N”. 

 

Fig. 10 

Tub Electrical Box 

LINE DISTRIBUTION BAR 

Содержание Cascade Aqua-Aire

Страница 1: ...45 Revision F 02 04 08 1 866 PENNERS 1 866 736 6377 1 800 732 0717 E mail Address pennersales hamilton net Web Site www pennerpatientcare com Cascade End Opening Tub TUBS 360010 1 360010 1L 360010 1W 360010 X 360010 XL and 360010 XW 361910 1 361910 X 362010 1 362010 1L 362010 X 362010 XL RESERVOIRS 370000 1W 370000 1WL 370000 XW 370000 XWL Cascade Wide Tub ...

Страница 2: ... AND COLD WATER SUPPLY REQUIREMENTS 7 ELECTRICAL REQUIREMENTS 7 UNPACKING THE TUB 7 UNPACKING THE RESERVOIR 8 TUB MODIFICATIONS FOR RESERVOIR 8 ASSEMBLING THE RESERVOIR 8 WATER SUPPLY HOSE CONNECTIONS 9 ANCHORING THE TUB RESERVOIR 9 WATER SUPPLY AND DRAIN CONNECTIONS 9 ELECTRICAL CONNECTIONS 10 FINISHING UP 11 TUB AND RESERVOIR CONTROLS 12 ...

Страница 3: ...he seat end of the tub Meaning Safety warning Failure to understand and obey this warning may result in injury to you or to others Meaning Failure to follow these instructions may cause damage to parts or systems Note Refer to the Tub Controls section of this manual for the location of any of the controls referenced Basic Room Dimensions Figure 1 shows a room layout for a Standard Cascade tub with...

Страница 4: ...4 4 Figure 3 Room layout for Standard Cascade with a Wide Reservoir Figure 4 ...

Страница 5: ...5 5 Room layout for Wide Cascade with a Wide Reservoir Figure 5 Room layout Side View for Cascade with Wide Reservoir Figure 6 Room Layout Side View for End Opening Cascade ...

Страница 6: ...s drain pipe is approximately 11 from the wall and 5 1 4 above the floor Figure 8 shows two different options for roughing in the drain pipe from the floor or from the wall Plumbing Requirements It is required that a licensed plumber make all plumbing connections He can select the best method of connection and if Reduced Pressure Zone Backflow Preventers are required ...

Страница 7: ...SI Maximum supply Hot water temperature Consult local requirements for maximum allowed supply temperatures Not recommended over 120o F Electrical requirements The Cascade tub Aqua Air with reservoir is rated 7 25 amps at 120 Volts AC A 15 amp GFCI circuit is required The optional Cascade reservoir is rated at 75 amp and is connected to the tub s electrical box via hard wiring Unpacking the tub 1 R...

Страница 8: ...cked with the reservoir The off white trim can be discarded 2 Remove the black hole plug located just above the overflow escutcheon by removing the plastic nut This plug and nut can be discarded 3 Replace the plug with the reservoir outlet fitting Gasket and outlet adapter These are packed with the reservoir See figure 9 for assembly order Ensure that the opening of the outlet fitting is pointed d...

Страница 9: ... the tub reservoir in the final installation position The reservoir should be against the wall 2 Locate and mark on the floor the location of the tub anchoring points two 3 8 diameter holes in the return flange located inside the large access doors on the tub If installing a tub with reservoir there are also two anchoring points for the reservoir These are located in the return flanges just inside...

Страница 10: ...it interrupter 1 Remove the covers from the electrical box of the tub and reservoir 2 For tubs with reservoirs connect the reservoir electrical supply lead to the tub s electrical kit a Remove the hole plug from the left side of the tub electrical box b Run the cable lead through that hole and secure using the cord restraint and nut provided c Connect the line wire to the line distribution bar loc...

Страница 11: ... there is a sound like a running motor immediately switch OFF the circuit breaker Find the Aqua Aire button on the control panel of the tub and press it once Switch on the tub circuit breaker The motor should not be running now Finishing up 1 Once the tub reservoir has been connected to the drain checked for leaks and fixed if needed and is connected to power the access doors can be installed Warn...

Страница 12: ...hower ON button The unit has a time adjustable automatic shut off 10 Hand shower sprayer 11 Aqua Air ON OFF button 12 Bath oil dispensing pump plunger 13 Shampoo dispensing pump plunger 14 Bath oil dispensing spout 15 Reservoir outlet 16 Shampoo dispensing spout 17 Drain plug cable 18 Reservoir fill lever 19 Reservoir fill on button 20 Reservoir fill off button On Reservoir equipped units only 8 9...

Страница 13: ...r nearest distributor contact PENNER PATIENT CARE INC Box 523 102 Grant St Aurora NE 68818 1 866 PENNERS 1 866 736 6377 1 800 732 0717 E mail Address pennersales hamilton net Web Site www pennerpatientcare com ...

Отзывы: