www.PennBarry.com
11
OPTIONS & ACCESSORIES
Fatrap Configuration
Fatrap configured fans are ideal for use in commercial kitchens over grilles, charcoal broilers, deep fat fryers, steam tables, ranges,
dishwashers, and other appliances. Fumex fans are specially configured for food service applications with the addition of a group of
accessories that either meets a requirement or eases installation requirements according to NFPA 96. NFPA 96 “Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations” is the generally recognized authority nationwide for restaurant installation
requirements. However, local codes may vary.
Included in the units are the following.
• UL 762 Listing: Fatrap configured Fumex fans are listed at 400°F — 100°F higher than UL requirements. The high temperature rating
is the result of the fan’s highly efficient forced motor cooling capability. Three direct drive (sizes 13 – 18) and all belt drive models are
listed.
• Pre-wired Junction Box: A weather-proof junction box is factory wired and mounted to the housing exterior. An appropriately sized
service switch is commonly selected as an additional option. These items meet the code requirements for positive electric shut-off.
• Grease Collector/Separator Box: Designed for easy installation, the grease is routed from a single swiveling collection spout to an
amply sized durable galvanized steel box, trapping grease and residue and avoiding discharge onto the roof surface. Additionally,
these boxes separate the water from the grease, prolonging the time required between periodic maintenance.
Additional Fatrap Accessories
Ventilated Curbs and Pedestals: For buildings two stories or higher NFPA 96 requires the use of ventilated mounting curbs or pedestals to
provide an approved arrangement for connecting a range hood and duct work to the roof fan. PennBarry’s ventilated mounting curbs and
pedestals, 18” high, comply with that standard when properly installed. Ventilated curbs have a flat mounting flange for fastening directly
to the roof deck. This flange should be securely fastened and flashed to ensure weather tightness. Ventilated pedestals are designed to
fit on an existing curb. They provide cap flashing when so installed.