PelPro Pellet Stove • 8104-171B • 10/21
PelPro Pellet Stove • 8104-171B • 10/21
8
9
Installing
Your
Stove
Installing
Your
Stove
Vent Termination Clearances
Installing Your Stove
A
D.
B
L
C
K
J
B
I
H
G
F
Clearances
A
12”
Clearance above grade, veranda porch, deck or balcony (Including vegetation and mulch)
B
12”
Clearance beside or below any windows or doors that open
12”*
Clearance above any window or door that opens
C
18”
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet
from the center line of the terminal
D
12”
Clearance to an outside corner wall
F
12”,
48” no outside air kit
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other
Stove
G
36”
Clearance to a mechanical air supply inlet
H
84”**
Clearance above a paved sidewalk or paved driveway located on public property
I
12”**
Clearance under a veranda, porch, deck or balcony
J
12”
Clearance above the roof
K
24”
Clearance from an adjacent wall including neighboring buildings
L
36” within a height of 15
feet above the meter /
regulator assembly
Clearance to each side of center line extended above natural gas or propane meter / regulator assembly
or mechanical vent
NOTICE:
Do NOT terminate vent:
•
In any location that will allow flue gases or soot from
entering or staining the building
•
In any location which could create a nuisance or hazard
•
In any enclosed or semi-enclosed area such as a
carport, garage, attic, crawl space, under a sun deck or
porch or narrow walkway
•
Closely fenced area, or any location that can build up
a concentration of fumes such as a stairwell, covered
breezeway, etc.
NOTICE:
Do NOT terminate below an air inlet.
•
It is recommended that at least 60” (1.52m) of vertical
pipe be installed when Stove is vented directly through
a wall—this will create a natural draft, which will help
prevent the possibility of smoke or odor venting into the
home during a power outage
•
It will also keep exhaust from causing a nuisance
or hazard by exposing people or shrubs to high
temperatures
•
The safest and preferred venting method is to extend
the vent vertically through the roof or above the roof
*Recommended to prevent condensation on windows and thermal breakage. **This is a recommended distance. For additional requirements check local codes.
Placing Your Stove
It is necessary to install
EMBER PROTECTION
; a Type 1 floor protector for this Stove.
The Floor protector must be non-combustible material, extending beneath Stove with a minimum
of 6
inches (152mm) in front of glass and 6 inches (152mm) to both sides of the fuel loading
door. Open the door and measure 6 inches (152mm) from the side edge of the opening in the
face of the Stove.
Installing Your Stove
1
1
2
Notice:
Be careful to protect the bottom of the Stove and floor surfaces when moving the Stove. Bottom
edges of Stove are sharp and can scratch surfaces.
Notice:
Clearances may only be reduced by means approved by the regulatory authority having jurisdiction.
USA Hearth Pad Requirements
Inches
mm
A
Sides
2
51
B
Back
2
51
C
Front
6
152
Non-combustible floor protection extending beneath the flue pipe is required with horizontal venting or under the top vent
adapter with vertical installation.
*Non-combustible floor protection must extend 2 inches (51mm) beneath the flue pipe when installed horizontal venting or
under the top vent adapter with vertical installation. CANADA REQUIRED, USA RECOMMENDED.
Canada Hearth Pad Requirements
Inches
mm
A
Sides
6
152
B
Back
2
51
C
Front
6
152
Hearth pad minimum requirements:
2
B*
A
C
A