Page 21
USE AND MAINTENANCE MANUAL
Rev. 02-18
PLUS
100
AB
CAS
Piercing temperature probe value
correction
-
10…+10
0
Pc
Compressor protection contact status
0 = NO
1 = NC
0 = NO
doC
Compressor safety time for door switch
:
when the door is opened the evaporator
fans shut down and the compressor will
continue working for time
doC
, after which it
will shut down.
0…5 minutes
0
Fst
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
read by the
evaporator
sensor is higher
than this value.
-
45…+45 °C
+45°C
tA
NO
– NC
alarm relay switching
0 = activates when alarm is
on
1 = deactivates when alarm is
on
1
rA
Control relay
door anti-fogging element
0 = alarm relay
1 = anti-fogging element on
0
in2
Man in cold room alarm
Select input INP2 on the board as
end of
remote defrost
or as
man in cold room
alarm
(contact NC).
0 = remote defrost end
1 = man in room alarm
0
Lic
Lower temperature set-point limit
-45.. LSc
-45°C
LSc
Upper temperature set-point limit
Lic..+45
+45°C
dMY
Day-month-year setting
day-month-year
-
hMS
Clock setting
Hour
–min-sec
-
CHAP. 5
– Parameter programming