![Pego PLUS100 AB Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/pego/plus100-ab/plus100-ab_use-and-maintenance-manual_1522017015.webp)
Page 15
USE AND MAINTENANCE MANUAL
Rev. 02-18
PLUS
100
AB
Program PR4: time-based cooling
Program for product cooling by time. Cooling ends when the maximum time Ab4 has
expired. When cooling is over the controller automatically goes to storage mode with the
ST4 setting. ST4 also has the function of regulating the compressor, which stops if room
temperature reaches temperature ST4-r1. The compressor is reactivated on reaching
temperature ST4.
Program PR5: time-based freezing
Product freezing program by time. Freezing ends when maximum time Ab5 has expired.
When freezing is over the controller automatically goes to storage mode with the ST5
setting. The compressor works continuously.
VARIABLES
MEANING
VALUES
DEFAULT
ST4
Storage temperature at end of cooling / lower
compressor stop limit (- differential r1)
The compressor stops during cooling if the ambient
temperature drops below ST4-r1. The fans continue to run.
-45 +45 °C
5°C
Ab4
Maximum safety duration of PR4 cooling
0:10:00…10:00:00
4:00:00
VARIABLES
MEANING
VALUES
DEFAULT
ST5
Storage temperature setting at end of freezing
The compressor does not stop for the entire duration of
freezing
-45 +45 °C
-20°C
Ab5
Maximum duration of PR5 freezing
0:10:00…10:00:00
1:00:00
CHAP. 5
– Parameter programming