background image

200NANO3CF**    

Termoregolatore elettronico / Electronic thermostat

        

Expert 

nano LINE

 

Manuale d’uso e manutenzione / Use and maintenance manual     

PEGO S.r.l. 

Via Piacentina, 6/b - 45030 -  ROVIGO 

Tel : +39(0)425 762906 - Fax: +39(0)425 762905 

www.pego.it   -  e-mail: [email protected] 

 

200NANO3CF_01-19_ITA_ENG  #  Rev.01-19  #  18/02/2019 

Manuale d’uso e manutenzione / Use and maintenance manual

 

 
 
LIST OF FIRST LEVEL VARIABLES (User level) 

Var 

MEANING 

DEF. 

r0

 

Temperature  differential  in  relation  to  principal 

SET-POINT 

< Range: 0.2 ÷ 10°C > 

Expressed in absolute  values and  defines  hysteresis 

(positive  if  mOd=0/2  or  negative  if  mOd=1/3)  of 

temperature in relation to SET POINT. 

d0 

Defrosting interval 

< Range: 0 ÷ 24 hours > 

If d0=0 defrosting is excluded. 

d2 

Defrosting end set point 

< Range:-35 ÷ 45°C >

 

Defrosting is not performed if the temperature read 

by the  defrosting probe  is higher than  value  d2. (In 

the  event  of  a  defective  probe,  defrosting  is 

performed on a time basis.) 

 

15 

d3 

Maximum defrosting time 

< Range: 1 ÷ 240 min >

 

25 

d7 

Dripping duration 

< Range:0 ÷ 10 min >

 

At completion of defrosting the compressor and fans 

remain inactive for the set period of time d7 and the 

defrosting LED on the front of the board flashes. 

 

F5 

Fan stop after defrosting

 

< Range: 0 ÷ 10 min >

 

Keeps  fans  inactive  for  a  period  of  time  F5  after 

dripping.  This  period  is  timed  from  the  end  of 

dripping. If dripping is not set, the fans pause directly 

after defrosting. 

 

A1 

Minimum temperature alarm

 

< Range: - 45 ÷ (A2-1)°C >

 

Absolute  temperature  referred  to  by  the  ambient 

probe  below  which,  following  the  ALD  delay,  the 

LOW  temperature alarm  is  triggered,  activating  the 

buzzer  (if  present)  and  showing  the  letters  EL 

alternating with the temperature on  the  display, as 

well as the flashing alarm icon. 

-45 

A2 

Maximum temperature alarm 

< Range: (A1+1) ÷ 99°C  >

 

Absolute  temperature  referred  to  by  the  ambient 

probe  above  which,  following  the  ALD  delay,  the 

HIGH temperature alarm is triggered, activating the 

buzzer  (if  present)  and  showing  the  letters  EH 

alternating with the temperature on  the  display, as 

well  as  the  flashing  alarm  icon.  When  the  alarm  is 

reset the alarm icon remains on without flashing to 

indicate that the event occurred, until the UP key is 

pressed. 

99 

tEu 

Evaporator/condenser probe temperature display

 

< °C  >

 (does not display anything if dE =1) 

reading 

only 

 

LIST OF SECOND LEVEL VARIABLES (Installer level) 

Var 

MEANING 

DEF. 

F3 

Fan status with compressor off

 

< Range: 0 ÷ 1 > 

0 = Fans in continuous operation 

1 = Fans ON only with compressor ON 

F4 

Fan pause during defrosting 

< Range: 0 ÷ 1 >

 

0 = Fans ON during defrosting 

1 = Fans OFF during defrosting 

Fst 

FAN disable TEMPERATURE 

(If dE = 0)

 

< Range: - 45 ÷ 99°C >

 

The  fans  remain  disabled  if  the  temperature  value 

read by the evaporator probe is higher than the value 

of  this  parameter.  The  fans  are  re-enabled  with  the 

evaporator probe deactivated or in error mode. 

DIRTY CONDENSER temperature alarm

 (If dE = 2) 

<Range: -45 

÷

 99 ° C> 

The  control  signals  "Ech"  alarm  if  the  temperature 

value  read  by  the  auxiliary  probe  is  higher  than  the 

value  of  this  parameter.  The  "Ech"  alarm  does  not 

alter the operation of the controller. 

45 

Fd 

Fst. differential 

< Range:

 1 

÷ 

10°C

 >

 

dE    

Evaporator / auxiliary probe setting 

< Range: 0 ÷ 2 > 

0 = Evaporator probe 

1 = Disabled 

By excluding the evaporator  probe,  defrosting  occurs 

cyclically based on d0 period and terminates upon the 

elapse of d3 time. 

2 = alarm  dirty condenser probe (see parameters 

Fst and Fd). 

 

d1  

Defrosting type 

< Range: 0 ÷ 1 >

 

0 = Heating element 

1 = Cycle inversion (hot gas) 

2 = Heater with temperature control 

dPo 

Defrost at Power-on 

< Range: 0 ÷ 1 >

 

0 = Disabled 

1 = Defrost at Controller power on (if possible)

 

dSE 

Smart defrost  

0 = disabled                      1 = enabled

 

dSt 

Smart defrost Setpoint (if dSE=1) 

< Range: -30 ÷ 30°C >

 

The  counting  of  the  time  between  the  defrosts  is 

incremented  only  if  the  compressor  is  ON  and  the 

evaporator temperature is less than dSt. 

C1 

Minimum time between each turning off and on of 

the compressor

 

< Range: 0 ÷ 15 min >

 

CE1 

Duration of compressor ON time in the case of faulty 

ambient probe

 (emergency mode).  

< Range: 0 ÷ 240 min / 0=Disabled > 

If CE1=0 the emergency mode in the presence of error 

EO remains disabled, the compressor remains off and 

defrosting  is  prevented  in  order  to  conserve  the 

remaining cold. 

CE2 

Duration  of  compressor  OFF  time  in  the  case  of 

faulty ambient probe

 (emergency mode).  

< Range: 5 ÷ 240 > 

doC 

Compressor timeout due to door switch opened

 

< Range: 0 ÷ 5 min >

 

When the door switch opens, the evaporator fans 

turn off and the compressor continues to function 

for a period doC, after which it turns off. 

Tdo 

Compressor re-activation time after door opened 

< Range: 0 ÷ 240 min / 0=Disabled > 

When  the  door  switch  opens  and  after  the  time 

tdo,  normal  function  of  the  control  is  restored, 

generating the door open alarm (Ed). 

mOd

 

Thermostat functioning mode    

< Range: 0 ÷ 3 >

 

0 =   Cold function  (NTC probe) 

1 =   Hot function   (NTC probe) 

2 =    Cold function  (PTC probe) 

3 =    Hot function   (PTC probe) 

(if mode=1 or 3 defrosting and fan disable Fst are 

excluded) 

in1 

Digital Input DI and activation mode setting 

< Range: -6 ÷ 6 > 

 6= Stop defrosting remotely (N.O.) 

(reads leading edge of impulse) 

 5= Start defrosting remotely (N.O.) 

(reads leading edge of impulse) 

 4= Stand-by remotely (N.O.) 

(In  order  to  indicate  Stand-By  mode,  the  display 

shows IN4 alternating with the current view) 

 3= Man-in-room alarm (N.O.) 

 2= Door switch  (N.O.) 

 1= Compressor protection (N.O.) 

 0= Disabled 

-1= Compressor protection (N.C.) 

-2= Door switch (N.C.) 

-3= Man-in-room alarm (N.C.) 

-4= Stand-by remotely (N.C.) 

(IN4  alternating  with  the  current  view  is  displayed 

to indicate stand-by mode) 

-5= Start defrosting remotely (N.C.) 

(reads leading edge of impulse) 

-6= Stop defrosting remotely (N.C.) 

(reads leading edge of impulse)

 

dO2 

Digital Output DO2 setting 

< Range: 0 ÷ 3 >

 

0= Defrosting heating elements output 

1= Room light output 

2 = alarm - it opens when the alarm is triggered 

3 = alarm - it closes when the alarm is triggered

 

LSE 

Minimum value attributable to set point 

< Range:

 -45 ÷ (HSE-1) °C

 >

 

-45 

HSE 

Maximum value attributable to set point 

< Range:

 +99 ÷ (LSE+1) °C

 >

 

45 

BEE 

Buzzer enable 

0 = disabled                       1 = enabled 

CAL 

Ambient probe value correction 

< Range:

 -10 ÷ 10 °C

 >

 

0.0 

Ald 

Delay time for signalling and display of minimum 

and maximum temperature alarm 

< Range: 0 ÷ 240 >

 

120 

AtE 

Temperature alarm Enable 

0 = always enabled 

1 = disabled if stand by active 

2 = disabled if door switch active 

3 = disabled if door switch or stand by active 

Ad 

Network address for connection to TeleNET or 

Modbus supervision system 

< Range: 

 

0 ÷ 31    (SEr=0) 

 

 1 ÷ 247  (SEr=1)  >

 

SEr 

RS-485 communication protocol 

0= TeleNET protocol 

1= Modbus-RTU protocol

 

Bdr 

Modbus baudrate 

0 = 300 baud 
1 = 600 baud 
2= 1200 baud 

3 = 2400 baud 
4 = 4800 baud 
5 = 9600 baud 

6 = 14400 baud 
7 = 19200 baud 
8 = 38400 baud

 

P1 

Password: protection type 

( active when PA is different from 0) 

0= Displays only the set point and allows alarm stop 

1= Displays the set point, allows alarm stop, + defrost 

+ light 

2= Blocks access to levels 1 and 2 during programming 

(all other functions permitted) 

3= Blocks access to level 2 during programming (all 

other functions permitted)

 

PA 

Password 

(see P1 for protection type) 

< Range: 0 ÷ 999 / 0=Disabled >

 

reL  Release software

 

read 

only 

THERMOSTAT FUNCTION MODES (mOd) 

The  variable  Mod  allows  the  selection  of  function  mode  of  the 

thermostat, in particular: 

COLD MODE (Mod =0 NTC or Mod =2 PTC) 

The DO1 output is activated when the temperature measured by 

the  ambient  probe  reaches  or  exceeds  the  SET  POINT+r0  value 

and  remains  active  until  the  temperature  drops  below  the  SET 

POINT. In this mode, the DO1 output is linked to the cold function 

icon. 

HOT MODE (Mod=1 NTC or Mod=3 PTC) 

The DO1 output is activated when the temperature measured by 

the  ambient  probe  reaches  or  exceeds  the  SET  POINT-r0  value 

and remains active until the temperature increases and exceeds 

the SET POINT. In this mode, the DO1 output is linked to the hot 

function icon; defrosting and fan stop FSt are DISABLED.

 

DIGITAL OUTPUT FUNCTION SETTINGS (dO2) 

The variable dO2 allows the allocation four possible functions to 

digital output DO2 on the basis of its value: 0=defrosting heating 

elements  output,  1=room  light  output,  2=  opens  when  the 

alarm is triggered and 3= closes when the alarm is triggered. 

In systems with off-cycle or fan defrosting, therefore, dO2=1 can 

be set to enable the UP key function for the room light. If this key 

is pressed for longer than 3 sec, it activates/deactivates the room 

light (output DO2) and controls the relative ROOM LIGHT icon. If 

the  light  is  manually  turned  on/off,  a  BIP  is  generated  as 

confirmation.  When  configured  for  the  room  light,  the  dO2 

output is automatically activated  when  the  door switch input  is 

active  or  the  man-in-cell  alarm  is  triggered  (E8).  Set  dO2=2  or 

dO2=3 to configure DO2 as alarm, as an alternative to defrost or 

light output. 

PASSWORD FUNCTION

 

The password function is activated by entering a value other than 

0 for the PA parameter. See parameter P1 for various protection 

levels.  The  protection  is  activated automatically  if  the  keyboard 

remains inactive for about 30 seconds. The figure 000 appears on 

the display. Use the up/down keys to change the number and the 

SET key to confirm. The password entry template 000 disappears 

if the keyboard is not activated within 30 seconds. 

If you forget the password, use the universal number 100. 

EMERGENCY MODE IN THE CASE OF ERROR E0

 

This safety mode guarantees the functioning of the compressor 

even  in  the  case  of  a  faulty  ambient  probe  (error  EO).  If  probe 

errors E0 and CE1 are different to 0, the compressor functions in 

operation  pause  mode,  with  compressor  ON  for  the  time  CE1 

and  OFF  for  the  time  CE2.  If  CE1>0  in  the  case  of  error  E0, 

defrosting is performed in normal functioning mode. If CE1=0 the 

emergency  mode in  the  presence of error  E0  remains  disabled. 

The  compressor  remains  off  and  defrosting  is  prevented  to 

conserve  the  remaining  cold.  Eliminate  as  soon  as  possible  the 

cause of error E0 and reactivate the control’s normal function for 

a correct temperature adjustment. 

MANUAL DEFROSTING ACTIVATION

 

To activate defrosting simply press the DOWN key for more than 3 

seconds; this activates the heating elements relay. Defrosting is not 

activated  if  the  appropriate  conditions  are  not  present  (end-of-

defrosting  temperature (d2) set lower than  the temperature  read 

by the evaporator probe). Defrosting terminates when the end-of 

defrosting  temperature  (d2)  is  reached  or  for  a  maximum 

defrosting time (d3) or by manually forced end-of-defrosting (end-

of-defrosting key or digital input). 

MANUALLY FORCED END OF CURRENT DEFROSTING

 

Pressing  the  DOWN  key  for  3  seconds  during  defrosting  forces 

the end of the current defrosting. In the case of manual end-of-

defrosting, dripping is also excluded. 

HOT GAS DEFROSTING

 

Set  the  parameter  d1  =1  to  control  inversion  cycle  defrosting.   

During the entire defrosting process the compressor and defrost 

relays  are  activated.  For  a  correct  control  of  the  system,  the 

installer  must  use  the  defrost  output  which  must  allow  the 

opening  of  the  inversion  cycle  electrovalve  and  closing  of  the 

liquid  electrovalve.  For  capillary  systems  (without  thermostatic 

valve)  it  is  sufficient  to  control  the  inversion  cycle  electrovalve 

using the defrost relay command. 

HEATER DEFROST BY TIME WITH TEMPERATURE CONTROL 

Set  the  parameter    d1  =  2  for  the  management  of  heater 

defrost by time with temperature control. During the defrost 

the  outputs  are  activated  when  the  evaporator’s 

temperatures  are  lower  than  d2.  Defrost  stops  after  d3 

minutes.  It  allows    energy  saving  and  a  better  defrost 

process. 

AMBIENT  TEMPERATURE  DISPLAY  DURING  AND  AFTER 

DEFROSTING 

During  defrosting  and  for  a  minute  following  the  end  of 

defrosting,  the  display  continues  to  display  the  last  ambient 

temperature value read before start of defrosting.

  

 

RS-485 CONNECTION

 

Connection  to  a  RS485  network  must  be  chain  type,  avoiding 

star connections and observing A and B polarity. It is advisable 

to use BELDEN 8762 cables. The configuration of the device in 

the  TeleNET  program  is  performed  by  entering  the  module 

name such as “

Expert Nano 3 CF device

” and assigning to it the 

same  network  address  entered  in  the  variable  Ad.  For  a 

Modbus-RTU  network  connection  and  for  details  on  the 

protocols of these devices, refer to the manual “MODBUS-RTU_ 

NANO_3CF” which can be downloaded from our internet site at 

www.pego.it

 

DIAGNOSTICS 

In the case of faults, the “Expert nano” control unit informs the 

operator by means of alarm codes shown on the display and an 

acoustic  signal  emitted  by  the  buzzer  (if  present).  The  acoustic 

alarm  can  be  stopped  by  pressing  the  UP  key  (the  error  code 

remains) and can be reactivated by pressing the SET key. In the 

event of an alarm, one of the following messages is displayed: 

ALARM CODE TABLE 

Var 

MEANING 

E0

 

Functional fault of ambient probe. 

E1 

Functional fault of defrosting probe (in this case, any defrosting 

processes will have a duration equal to time d3) or condenser 

probe. 

E2 

EEPROM memory error.  All outputs are deactivated except for 

alarm outputs if present. 

E8 

Man-in-room alarm. 

Ec 

Compressor protection alarm (e.g. thermal protection or max. 

pressure  switch).  All  outputs  are  deactivated  except  for  the 

alarm output if present. 

Ed 

Door open  alarm.  When  the  door  switch  opens  and  the  tdo 

time  has  elapsed,  normal  function  of  the  control  is  reset, 

triggering the door open alarm (Ed). 

EL 

Minimum  temperature  alarm.  The  letters  EL  flash  alternating 

with the temperature (see parameter A1). 

EH 

Maximum temperature alarm. The letters EH flash alternating 

with the temperature (see parameter A2). 

Ech 

Dirty condenser alarm (dE = 2). Non-blocking. 

 

E N G L I S H  

 

Отзывы: